TECHNICAL & SERVICE MANUAL Series PEAD R407C/R410A <indoor unit> Service ref. • Refer to the OCT04 as for control relation.This manual does not cover Models PEAD-RP1.6EA outdoor units. PEAD-RP2EA When servicing them, please refer to the service manual PEAD-RP2.5EA OC261 REVISED EDITION-B,...
SAFETY PRECAUTION CAUTIONS RELATED TO NEW REFRIGERANT <Cautions for units utilizing refrigerant R410A> Use new refrigerant pipes. Do not use refrigerant other than R410A. n case of using the existing pipes for R22, be careful with f other refrigerant (R22 etc.) is used, chlorine in refrige- the following.
Page 4
[2] Additional refrigerant charge When charging directly from cylinder Ensure that the cylinder for R410A is syphon type. Charging should be performed with the syphon cylinder type stood vertically. (Refrigerant must be charged from liquid phase.) Unit ravimeter [3] Service tools Use the below service tools as exclusive tools for R410A refrigerant.
PART NAMES AND FUNCTIONS Indoor Unit • Air intake (sucks the air inside the room into the unit) Air outlet In case of rear inlet In case of bottom inlet (Only 1.6~2.5HP)
• Remote controller • Once the operation of the unit is set, subsequent operations can be performed only by pressing the ON/OFF button repeatedly. [Operation buttons] 1Hr. CENTRALLY CONTROLLED ON OFF ˚C CLOCK CHECK FILTER CHECK MODE ˚C TEST RUN STAND BY ERROR CODE FUNCTION...
Page 7
[Display] CENTRALLY CONTROLLED 1Hr. ON OFF ˚C CLOCK CHECK FILTER CHECK MODE ˚C TEST RUN STAND BY ERROR CODE FUNCTION NOT AVAILABLE DEFROST TEMP. ON/OFF IKLJ Current time/Timer Not available function Centralized control Ventilation Timer ON Function setting mode Abnormality occurs Test run mode Error check mode Operation mode:...
OUTLINES & DIMENSIONS 1. INDOOR UNIT PEAD-RP1.6, 2, 2.5EA Model FOR PUHZ-RP TYPE:6.35 FOR PUHZ-RP TYPE:1 .7 RP1.6, FOR PU(H)-P TYPE:9.5 FOR PU(H)-P TYPE:15.88 RP .5 1070 1044 15.88 Service space:500 or more 10- ¿3 (1.6, HP) 1 - ¿3 ( .5HP) 50~150 Refrigerant piping flare connection (liquid F copper tube):HP Access door...
TROUBLE-SHOOTING 9-1. TROUBLE-SHOOTING <Error code display by self-diagnosis and actions to be taken for service (summary)> Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit. Actions to be taken for service, which depends on whether or not the inferior phenomenon is reoccurring at service, are sum- marized in the table below.
9-2. SELF-DIAGNOSIS ACTION TABLE Note: Refer to the manual of outdoor unit for the details of display such as F, U, and other E. Error Code Meaning of error code and detection method Judgment and action Case 1 Defective thermistor character- 1–3 Check resistance value of thermistor.
Page 44
Error Code Meaning of error code and detection method Judgment and action Case Freezing/overheating protection is (Cooling or drying mode) (Cooling or drying mode) 1 Clogged filter (reduced airflow) working 1 Check clogs of the filter. 1 Freezing protection (Cooling mode) 2 Short cycle of air path 2 Remove shields.
Page 45
Error Code Meaning of error code and detection method Judgment and action Case 1 Defective thermistor character- Abnormality of pipe temperature ther- 1–3 Check resistance value of thermistor. mistor / Condenser-Evaporator (TH5) istics For characteristics, refer to (P1) above. 2 Check contact failure of connector 1 The unit is in three-minute resume pro- 2 Contact failure of connector Put the power on and check restart after...
Page 46
9-3. TROUBLE-SHOOTING BY INFERIOR PHENOMENA Note: Refer to the manual of outdoor unit for the detail of remote controller. Phenomena Factor Countermeasure (1)LED2 on indoor control p.c. • When LED1 on indoor control p.c. board is also off. 1 Power supply of 220~240V is not supplied to outdoor 1 Check the voltage of outdoor power sup- board is off.
9-4. EMERGENCY OPERATION 9-4-1. When wired remote controller or indoor unit micro computer has trouble 1. If there is not any other item wrong when the trouble occures, emergency operation starts when the indoor control board switch (SWE) is set to ON. During the emergency operation the indoor unit is as follows;...
Page 48
9-5. TEST POINT DIAGRAM 9-5-1. Power board CN2S Connect to the Indoor controller board (CN2D) (DC12.6~15.4V) Earth support pad CN02 Connect to the Indoor controller board (CN03) Between 1 and 2 DC 0~24V (Indoor/Outdoor transmission) Between 2 and 3 AC 220~240V Fuse 4A/250V CN01 Connect to the Terminal Block (TB4)
Page 49
9-5-2. Controller board CN90 Connect to the wireless CN2D CN22 CN6V CN32 Connect to the indoor Remote controller con- remote controller Vane motor output Remote ON/OFF board/remote operation power board (CN2S) necting line (12 pulse) adaptor adaptor DC12.6~15.4V DC10.4~14.6V LED1 Display of supplied power for controller CN21...
Page 50
9-6. FUNCTIONS OF JUMPER WIRE Each function is controlled by the jumper wire on control p.c. board. For service parts, J11- J15 and J21-J24, DIP switches (SW1 and SW2) are equipped with jumper wire. (Marks in the table below) Jumper wire ( : Short : Open) DIP switch...
DISASSEMBLY INSTRUCTIONS Figure1. isconnect the fan motor connecter (and the booster heater connector) rain pan catches (Hidden) Heat exchanger Bottom plate Filter assembly rain pan catches (Hidden) Bottom plate rain pan 1. Removing the fan motor 5. Remove the fan base plate as follow: 1.
Page 52
Figure3. an base Sirocco fan Motor Housing Motor base assembly Bush (Only PEAD-RP3) Bush Piece Sirocco fan Piece Housing assembly...
OPTIONAL PARTS 1. PROGRAM TIMER Part No. PAC-YT32PTA 1-1. Names and functions <PAC-YT32PTA> MODE A MODE B M O NIT O R SET BACK SET/MONITOR MODE A/B/OFF SET BACK DAILY TIMER MODE A/B WEEKLY SETTING ON/OFF/SET BACK CLOCK TODAY PAC-YT32PTA DAILY SETTING A SET/MONITOR DISPLAY: 1 SET/MONITOR Button...
Page 60
2. REMOTE SENSOR Part No. PAC-SE41TS-E Applied model PEAD-RP1.6,2,2.5EA , PEAD-RP3,4,5,6EA 3. REMOTE OPERATION ADAPTER Part No. PAC-SF40RM-E Applied model PEAD-RP1.6,2,2.5EA , PEAD-RP3,4,5,6EA 4. REMOTE ON/OFF ADAPTER Part No. PAC-SE55RA-E Applied model PEAD-RP1.6,2,2.5EA , PEAD-RP3,4,5,6EA 5. OPTIONAL MOTOR The external static pressure of 130Pa allows long ducts to be used more extensively to enable the most convenient posi- tioning of indoor units.
Page 64