4

SPECIFICATIONS

4-1. Heat pump type (1)
Item
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan
Fan(drive) x No.
Fan motor output
Airflow(Low-Med2-Med1-High)
External static pressure
Operation control & Thermostat
Noise level(Low-Med2-Med1-High)
Unit drain pipe O.D.
Dimensions
Weight
OUTDOOR
Service Ref.
UNIT
Item
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan
Fan(drive) x No.
Fan motor output
Airflow(Low-Med2-Med1-High)
External static pressure
Operation control & Thermostat
Noise level(Low-Med2-Med1-High)
Unit drain pipe O.D.
Dimensions
Weight
OUTDOOR
Service Ref.
UNIT
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor
: D.B. 27˚C(80˚F), W.B. 19˚C (66˚F)
Heating : Indoor : D.B. 20˚C(68˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
Upper limit
Heating
Lower limit
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor Unit
Single phase 230V 50Hz
Outdoor Unit Single phase 230V 50Hz
Service Ref.
Btu/h
W
kW
kW
A
A
kW
K/min(CFM)
Pa(mmAq)
dB
mm(in.)
W
mm(in.)
mm(in.)
D
mm(in.)
H
kg(lbs)
Service Ref.
Btu/h
W
kW
kW
A
A
kW
K/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
W
mm(in.)
D
mm(in.)
H
kg(lbs)
Outdoor
Outdoor
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
D.B. 28˚C
D.B. 21˚C, W.B. 15˚C
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
9
PCA-RP2GA
Cooling
16,000
4,700(2,300~5,400)
1.67
PCA-RP2GA
Single phase, 50Hz, 220-230-240V
0.09
0.41
1.20
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 2
0.054
10-11-12-13(355-390-425-460)
0(direct blow)
Remote controller & built-in
37-38-40-42
26(1)
1,000(39-3/8)
680(26-3/4)
210(8-1/4)
27(60)
PUHZ-RP2VHA
PCA-RP2.5GA
Cooling
20,500
6,000(2,700~6,700)
1.63
PCA-RP2.5GA
Single phase, 50Hz, 220-230-240V
0.12
0.53
1.27
Munsell 0.70Y 8.59/0.97
Plate fin coil
Sirocco fan (direct) x 3
0.070
14-15-16-18(495-530-565-635)
0(direct blow)
Remote controller & built-in
37-39-41-43
26(1)
1,310(51-9/16)
680(26-3/4)
210(8-1/4)
34(75)
PUHZ-RP2.5VHA
: D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
: D.B. 7˚C(45˚F),
W.B. 6˚C (43˚F)
Outdoor
Heating
18,800
5,500(2,500~6,600)
1.71
0.09
0.41
1.20
Heating
23,900
7,000(2,800~8,200)
2.03
0.12
0.53
1.27

Hide quick links: