Appendix
A.8 Settings
A.8
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
Addr.
Parameter
0
FLEXIBLE FUNC.
0
OPERRAT. MODE
0
BLK f out of r
0
MEAS. QUANTITY
0
MEAS. METHOD
0
PICKUP WITH
0
CURRENT
0
VOLTAGE
0
POWER
0
VOLTAGE SYSTEM
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
0
P.U. THRESHOLD
454
Function
C
Flx
OFF
ON
Alarm Only
Flx
3-phase
1-phase
no reference
Flx
YES
NO
Flx
Please select
Current
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
dV/dt rising
dV/dt falling
Frequency
df/dt rising
df/dt falling
Binray Input
Flx
Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Flx
Exceeding
Dropping below
Flx
Ia
Ib
Ic
In
In sensitive
In2
Flx
Please select
Va-n
Vb-n
Vc-n
Va-b
Vb-c
Vc-a
Vn
Vx
Flx
Ia Va-n
Ib Vb-n
Ic Vc-n
Flx
Phase-Phase
Phase-Ground
Flx
0.05 .. 40.00 A
Flx
1A
0.05 .. 40.00 A
5A
0.25 .. 200.00 A
Flx
1A
0.001 .. 1.500 A
5A
0.005 .. 7.500 A
Flx
2.0 .. 260.0 V
Flx
2.0 .. 200.0 V
Flx
40.00 .. 60.00 Hz
Flx
50.00 .. 70.00 Hz
Flx
0.10 .. 20.00 Hz/s
Setting Options
Default Setting
OFF
3-phase
YES
Please select
Fundamental
Exceeding
Ia
Please select
Ia Va-n
Phase-Phase
2.00 A
2.00 A
10.00 A
0.100 A
0.500 A
110.0 V
110.0 V
51.00 Hz
61.00 Hz
5.00 Hz/s
E50417-G1140-C344-A5, Release date 11.2012
Comments
Flexible Function
Mode of Operation
Block while Freq. is out of range
Selection of Measured Quantity
Selection of Measurement
Method
Pickup with
Current
Voltage
Power
Voltage System
Pickup Threshold
Pickup Threshold
Pickup Threshold
Pickup Threshold
Pickup Threshold
Pickup Threshold
Pickup Threshold
Pickup Threshold
SIPROTEC, 7SK80, Manual