REM 610
3.2.2.2.
22
Motor Protection Relay
Operator's Manual
How to change settings
The actual settings consist of the settings of group 1 or group 2, depending on which
group that has been selected to be active (indicated by an asterisk "*"). The actual
settings can be seen in the first parameter menu, e.g. SETTINGS\PROTECT.
STAGES\ Is> In:x.xx.
Submenu
SETTINGS
Is>
In:x.xx
Fig. 3.2.2.2.-1 Setting parameters in setting group 1 and setting group 2
By switching between setting groups 1 and 2, the user can activate a whole group of
settings at the same time. Switch between the setting groups as follows:
• with the parameter GROUP 1/GROUP 2 under the main menu group
SETTINGS.
• with a digital input signal, provided that SGB1...5/4 has been set to 1 in both
setting groups (GRP1 and GRP2).
• with parameter V150 via the SPA bus.
When a large number of settings are to be altered, e.g. during commissioning of the
relay systems, use a PC equipped with the necessary software. If such is not
available, or when only a few settings are to be altered:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select the main menu group SETTINGS and the
desired group menu (e.g. PROTECT. STAGES), and press
3. Use
or
to select the parameter to be changed and press
4. Use
or
to select setting group 1 or 2 (GRP1 or GRP2). The active setting
group is indicated by an asterisk "*".
5. Enter the setting mode by pressing
default password 999 is still valid, no password will be required.
6. The first digit of the setting value of the parameter to be edited will start to flash.
Use
and
to move the cursor and
number.
7. To store a new value and return the display to the view mode, press
parameter is of a numerical kind, the display will confirm the storage by once
flashing "---" on the display.
8. To exit the setting mode without storing the changes, press
confirming and the display will be returned to the view mode.
9. Press
to return the display to the idle mode.
Parameter Menu
SETTINGS
* GRP 1
:x.xx
Confirm
GRP 2
:x.xx
Cancel
and give the password if required. If the
and
1MRS 752264-MUM
.
.
to increase or decrease the
. If the
once before