Revision: - suitable. The advanced automatic reclosing, 1. 650 series overview synchronizing, synchrocheck and energizing check functions of REQ650 provides an optimized stand alone product. This IED also The 650 series IEDs provide optimum 'off-the- enables well-structured and reliable protection shelf', ready-to-use solutions.
Page 4
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 132 kV Bus REQ650-A01A – Single Busbar Single breaker 10AI (4I+1I+5U) Three phase variant 132kV/110V Meter. V MMXU 289G 0->1 1->0 SYNC BKR1 SMB RREC SMP PTRC SES RSYN >...
Page 5
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 132 kV Bus REQ650-B11A – Double Busbar Single breaker 10AI (4I+1I+5U) Single phase variant 132kV/ 110V 132kV/ 110V Meter. V MMXU Meter. V MMXU 289G 0->1 1->0...
Page 6
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 132 kV Bus REQ650-B11A – Double Busbar Single breaker 10AI (4I+1I+5U) Single phase variant 132kV/ 110V 132kV/ 110V Meter. V MMXU Meter. V MMXU 289G 0->1 1->0...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 3. Available functions...
Page 8
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Back-up protection functions IEC 61850/ ANSI Function description Breaker Function block name Current protection PHPIOC Instantaneous phase overcurrent protection SPTPIOC Instantaneous phase overcurrent protection OC4PTOC 51/67...
Page 9
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 IEC 61850/ ANSI Function description Breaker Function block name Voltage protection UV2PTUV Two step undervoltage protection OV2PTOV Two step overvoltage protection ROV2PTOV 59N Two step residual overvoltage protection...
Page 10
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Control and monitoring functions IEC 61850/ ANSI Function description Breaker Function block name Control SESRSYN Synchrocheck, energizing check, and synchronizing SMBRREC Autorecloser STBRREC Autorecloser QCBAY Bay control...
Page 11
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 IEC 61850/ ANSI Function description Breaker Function block name I103POSCMD IED commands with position and select for IEC60870-5-103 Secondary system supervision CCSRDIF Current circuit supervision SDDRFUF...
Page 12
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 IEC 61850/ ANSI Function description Breaker Function block name FXDSIGN Fixed signal function block B16I Boolean 16 to Integer conversion B16IFCVI Boolean 16 to Integer conversion with...
Page 13
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 IEC 61850/ ANSI Function description Breaker Function block name MVEXP Measured value expander block SPVNZBAT Station battery supervision SSIMG Insulation gas monitoring function SSIML Insulation liquid monitoring function...
Page 14
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Designed to communicate IEC 61850/ ANSI Function description Breaker Function block name Station communication IEC 61850 communication protocol, LAN1 DNP3.0 for TCP/IP communication protocol, LAN1 IEC61870-5-103...
Page 15
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Basic IED functions IEC 61850/ Function description Function block name Basic functions included in all products INTERRSIG Self supervision with internal event list SELFSUPEVLST Self supervision with internal event list...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 directional or non-directional independently for 4. Current protection each of the steps. Instantaneous residual overcurrent Instantaneous phase overcurrent protection EFPIOC (50N) protection PHPIOC (50) The Instantaneous residual overcurrent...
Page 17
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 is significantly smaller than the short circuit Breaker failure protection (CCRBRF, 50BF) currents. In addition to this, the magnitude of current criteria can be fulfilled by one or two...
Page 18
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 on the disconnected part of the line. The Directional over/underpower primary line distance protection will thus not protection GOPPDOP/GUPPDUP be able to operate and must be blocked.
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 5. Voltage protection Loss of voltage check LOVPTUV (27) Loss of voltage check (LOVPTUV, 27) is Two step undervoltage protection suitable for use in networks with an automatic UV2PTUV (27) system restoration function.
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Rate-of-change frequency protection Fuse failure supervision SDDRFUF SAPFRC (81) The aim of the fuse failure supervision function Rate-of-change frequency protection function (SDDRFUF) is to block voltage measuring...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 be connected. It is used for slip frequencies Breaker close/trip circuit monitoring that are larger than those for synchronism TCSSCBR check and lower than a set maximum level for the synchronizing function.
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 function blocks LOCREM and LOCREMCTRL to single point commands, designed to bring in the Bay control (QCBAY) function block. A commands from REMOTE (SCADA) to those...
Page 23
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 • RSMEMORY function block is a flip-flop that Trip matrix logic TMAGGIO can reset or set an output from two inputs respectively. Each block has two outputs Trip matrix logic TMAGGIO function is used to where one is inverted.
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 configuration, initiating conditions, recording 10. Monitoring times, and large storage capacity. A disturbance is defined as an activation of an Measurements CVMMXN, CMMXU, input to the AxRADR or BxRBDR function...
Page 25
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 perspective (for example corrective actions) Event recorder DRPRDRE and long perspective (for example functional analysis). Quick, complete and reliable information about disturbances in the primary and/or in the...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 and accumulated energy. The energy is Station battery supervision calculated from the measured input currents as SPVNZBAT a sum of I 2 t values. Alarms are generated...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 The LHMI is simple and easy to understand. 12. Human Machine The whole front plate is divided into zones, interface each with a well-defined functionality: • Status indication LEDs •...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 In the IED, the internal time can be Authority status ATHSTAT synchronized from a number of sources: Authority status (ATHSTAT) function is an • SNTP indication function block for user log-on activity.
Page 29
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 available to any Ethernet based application via Table 1. Supported communication interface FTP in the standard Comtrade format. Further, and protocol alternatives the IED can send and receive binary values,...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 that can interpret IEC 60870-5-103 Flush mounting the IED communication messages. 15. Hardware description Layout and dimensions Mounting alternatives The following mounting alternatives are available (IP40 protection from the front): IEC09000672.ai...
Page 31
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Rack mounting the IED IEC09000673.ai IEC09000673 V1 EN IEC09000676.ai Figure 6. Flush mounted IED IEC09000676 V1 EN Figure 7. Rack mounted IED 222 mm 27 mm...
Page 32
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 IEC09000677.ai IEC09000677 V1 EN Figure 8. Two rack mounted IEDs side by side 224 mm + 12 mm with ring-lug connector 25.5 mm 482.6 mm (19") GUID-5C185EAC-13D0-40BD-8511-58CA53EFF7DE V1 EN Figure 10.
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 17. Technical data General Definitions Reference The specified value of an influencing factor to which are referred the value characteristics of the equipment Nominal The range of values of an influencing quantity (factor) within which, under...
Page 44
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Analog inputs Table 2. Energizing inputs Description Value Rated frequency 50/60 Hz Operating range Rated frequency ± 5 Hz Current inputs Rated current, I 0.1/0.5 A...
Page 45
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Auxiliary DC voltage Table 3. Power supply Description 600PSM02 600PSM03 100, 110, 120, 220, 240 V AC, 48, 60, 110, 125 V DC 50 and 60 Hz...
Page 46
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 5. Signal output and IRF output IRF relay change over - type signal output relay Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s...
Page 47
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 7. Power output relays with TCM function Description Value Rated voltage 250 V DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s...
Page 48
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 11. Serial rear interface Type Counter connector Serial port (X9) Optical serial port, type ST for IEC 60870-5-103 Influencing factors Table 12. Degree of protection of flush-mounted IED...
Page 49
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 15. Environmental tests Description Type test value Reference Cold tests operation 96 h at -25ºC IEC 60068-2-1/ANSI 16 h at -40ºC C37.90-2006 (chapter 4) storage 96 h at -40ºC...
Page 50
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Type tests according to standards Table 16. Electromagnetic compatibility tests Description Type test value Reference 100 kHz and 1 MHz burst IEC 61000-4-18 disturbance test IEC 60255-22-1, level 3 ANSI C37.90.1-2002...
Page 51
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 16. Electromagnetic compatibility tests, continued Description Type test value Reference • 3 s 1000 A/m • Continuous 100 A/m Power frequency immunity IEC 60255-22-7, class A...
Page 52
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 17. Insulation tests Description Type test value Reference Dielectric tests: IEC 60255-5 ANSI C37.90-2005 • Test voltage 2 kV, 50 Hz, 1 min 1 kV, 50 Hz, 1 min,...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 22. Instantaneous phase overcurrent protection SPTPIOC (50) Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (5-2500)% of lBase ±...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 23. Four step phase overcurrent protection OC4PTOC (51/67) Function Setting range Accuracy ± 1.0% of I Operate current (5-2500)% of lBase at I ≤ I ±...
Page 56
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 24. Four step phase overcurrent protection OC4SPTOC (51_67) Function Setting range Accuracy ± 1.0% of I at I £ I Operate current (5-2500)% of lBase ±...
Page 57
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 25. Instantaneous residual overcurrent protection EFPIOC (50N) Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ±...
Page 58
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 26. Four step residual overcurrent protection EF4PTOC (51N/67N) Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ±...
Page 59
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 27. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) Function Range or value Accuracy ± 1.0% of I at I £ I (0.25-200.00)% of lBase Operate level for 3I ·cosj...
Page 60
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 27. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) , continued Function Range or value Accuracy ± 2.0 degrees Relay characteristic angle (-179 to 180) degrees ±...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 28. Thermal overload protection, one time constant LPTTR (26) Function Range or value Accuracy ± 1.0% of I Reference current (0-400)% of IBase ± 1.0°C Reference temperature (0-600)°C...
Page 62
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 29. Breaker failure protection CCRBRF (50BF) Function Range or value Accuracy ± 1.0% of I at I £ I Operate phase current (5-200)% of lBase ±...
Page 63
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 31. Stub protection STBPTOC (50STB) Function Range or value Accuracy ± 1.0% of I at I £ I Operating current (1-2500)% of IBase ± 1.0% of I at I > I Reset ratio >...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 34. Directional over/underpower protection GOPPDOP, GUPPDUP (32/37) Function Range or value Accuracy Power level (0.0–500.0)% of SBase ± 1.0% of S at S < S ±...
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Voltage protection Table 36. Two step undervoltage protection UV2PTUV (27) Function Range or value Accuracy Operate voltage, low and high (1–100)% of VBase ± 0.5% of V...
Page 66
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 37. Two step overvoltage protection OV2PTOV (59) Function Range or value Accuracy Operate voltage, low and high (1-200)% of VBase ± 0.5% of V at V < V step ±...
Page 67
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 38. Two step residual overvoltage protection ROV2PTOV (59N) Function Range or value Accuracy Operate voltage, step 1 (1-200)% of VBase ± 0.5% of V at V < V ±...
Page 68
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Frequency protection Table 40. Under frequency protection SAPTUF (81) Function Range or value Accuracy Operate value, pickup function (35.00-75.00) Hz ± 2.0 mHz Operate value, restore frequency (45 - 65) Hz ±...
Page 69
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 42. Rate-of-change frequency protection SAPFRC (81) Function Range or value Accuracy Operate value, pickup function (-10.00-10.00) Hz/s ± 10.0 mHz/s Operate value, restore enable frequency (45.00 - 65.00) Hz ±...
Page 70
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 45. Breaker close/trip circuit monitoring TCSSCBR Function Range or value Accuracy Operate time delay (0.020 - 300.000) s ± 0,5% ± 110 ms Control Table 46. Synchronizing, synchronism check and energizing check SESRSYN (25)
Page 71
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 47. Autorecloser SMBRREC (79) Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Autoreclosing open time: shot 1 - t1 3Ph (0.000-60.000) s ±...
Page 72
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 48. Autorecloser STBRREC (79) Function Range or value Accuracy Number of autoreclosing shots 1-5 Autoreclosing open time: Shot (0.000-60.000) s ± 0.5% ± 25 ms...
Page 73
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 50. Tripping logic SPTPTRC (94) Function Range or value Accuracy Trip action 3-Ph, 1/3-Ph Timers (0.000-60.000) s ± 0.5% ± 10 ms Table 51. Configurable logic blocks...
Page 74
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Monitoring Table 52. Measurements CVMMXN Function Range or value Accuracy ± 0.5% of V Voltage (0.1-1.5) ×V at V£V ± 0.5% of V at V > V ±...
Page 75
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 54. Disturbance report DRPRDRE Function Range or value Accuracy Current recording ± 1,0% of I at I ≤ I ± 1,0% of I at I > Ir Voltage recording ±...
Page 76
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 55. Event list DRPRDRE Function Value Buffer capacity Maximum number of events in 1000 the list Resolution 1 ms Accuracy Depending on time synchronizing Table 56. Indications DRPRDRE...
Page 77
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 59. Disturbance recorder DRPRDRE Function Value Buffer capacity Maximum number of analog inputs Maximum number of binary inputs Maximum number of disturbance reports 100 Maximum total recording time (3.4 s recording time and...
Page 78
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 62. Insulation liquid monitoring function SSIML(71) Function Range or value Accuracy Alarm, oil level 0.00-25.00 Oil level lockout 0.00-25.00 Temperature alarm -40.00-200.00 Temperature lockout -40.00-200.00 Timers (0.000-60.000) s...
Page 79
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 66. Degree of protection of flush-mounted IED Description Value Front side IP 40 Table 67. Degree of protection of the LHMI Description Value Front and side...
Page 80
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Inverse time characteristics Table 69. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 unless otherwise stated æ...
Page 81
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 70. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç...
Page 82
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 72. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 Class 5 +40 ms unless otherwise stated æ...
Page 83
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 73. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 Class 5 +40 ms unless otherwise stated æ...
Page 84
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Table 74. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in Class 5 +40 ms steps of 0.01 æ...
To obtain the complete ordering code, please combine code from the tables, as given in the example below. Exemple code: REQ650*1.1-A01AX00-X00-B1A5-B-A-SA-AB1-RA3-AXXX-E. Using the code of each position #1-11 specified as REQ650*1-2 2-3-4 4-5-6-7 7-8 8-9 9-10 10 10 10-11 - 10...
Page 86
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Casing Notes and Rules Rack casing, 6 U 1/2 x 19" Selection for position #5. Mounting details with IP40 of protection from the front Notes and Rules No mounting kit included Rack mounting kit for 6 U 1/2 x 19"...
Page 87
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Connection type for Analog modules Notes and Rules Ringlug terminals Analog system Slot position: Transformer module, 4I, 1/5A+1I, 0.1/0.5A+5U, 100/220V Selection for position #9. Binary input/output module...
Page 88
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Manuals Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual, Installation manual, Commissioning manual, Application manual, Communication protocol manual, DNP, Communication protocol manual, IEC61850, Communication protocol manual, IEC60870-5-103, Type test certificate, Engineering manual and Point list manual, DNP3, Connectivity packages and LED label template is always included for each IED.
Page 89
Breaker protection REQ650 ANSI 1MRK 505 269-BUS - Product version: 1.1 Issued: April 2011 Reference information For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name: Voltage level:...
Page 91