Siemens siprotec 7SD610 User Manual page 278

Differential protection
Hide thumbs Also See for siprotec 7SD610:
Table of Contents

Advertisement

3 Mounting and Commissioning
i.e. one jumper (X61 to X64) for each input transformer of the phase currents and in
addition the common jumper X60.
Jumper X64 is plugged in position „IE".
Jumpers X71, X72 and X73 on the input/output board C-I/O-11 are used for setting the
bus address and must not be changed. The following Table lists the jumper preset-
tings.
Table 3-9
Slot of input/output board C-I/O-11: No. 2 in Figure 3-3.
278
Jumper settings of Bus Address of the input/output board C-I/O-11
Jumper
Presetting
X71
1-2(H)
X72
1-2 (H)
X73
2-3 (L)
7SD610 Manual