Relion 650 series, line distance protection
Hide thumbs Also See for REL650:

Advertisement

R E L I O N ® 650 SERIES
Line distance protection REL650
Version 2.2
Product guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB REL650

  • Page 1 — R E L I O N ® 650 SERIES Line distance protection REL650 Version 2.2 Product guide...
  • Page 2: Table Of Contents

    Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
  • Page 3: Application

    The packages are configured and ready for direct use. Analog GUID-6EFE28BF-7974-4A94-A7C2-AB43D48E1151 v3 REL650 is used for the protection, control and monitoring of and control circuits have been predefined and other signals overhead lines and cables in solidly or impedance earthed need to be applied as required for each application.
  • Page 4 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 REL650 A11 – Single breaker with single phase tripping 2AI (7I+5U) WA2_VT VN MMXU WA1_VT 1→0 1->0 SC/VC 5(0→1) VN MMXU SMP PTRC SMP PTRC SMB RREC SES RSYN...
  • Page 5 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Description of A12 GUID-FCF2C16D-D4CD-4812-B795-6052AE6C0C50 v1 REL650 A12 – Single breaker with single phase tripping for high ohmic and resonance earthed systems 12AI (7I+5U) WA2_VT VN MMXU WA1_VT 1->0 1→0...
  • Page 6 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1...
  • Page 7: Available Functions

    1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 are not exposed to the user or do not need 2. Available functions GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 to be configured are not described in this manual. The following tables list all the functions available in the IED.
  • Page 8: Current Protection

    1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v13 IEC 61850 or ANSI Function description Line Distance function name REL650 (A11) REL650 (A12) Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC Directional phase overcurrent protection, four steps...
  • Page 9: Secondary System Supervision

    1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v15 IEC 61850 or ANSI Function description Line distance function name REL650 (A11) REL650 (A12) Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC...
  • Page 10 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 IEC 61850 or ANSI Function description Line distance function name REL650 (A11) REL650 (A12) AND, GATE, INV, Basic configurable logic blocks (see Table 2) 40–420 40–420 LLD, OR,...
  • Page 11: Monitoring

    1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 IEC 61850 or ANSI Function description Line distance function name REL650 (A11) REL650 (A12) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement...
  • Page 12 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v15 IEC 61850 or ANSI Function description Line distance function name REL650 (A11) REL650 (A12) Station communication LONSPA, SPA SPA communication protocol LON communciation protocol HORZCOMM...
  • Page 13 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 IEC 61850 or ANSI Function description Line distance function name REL650 (A11) REL650 (A12) PCMACCS IED configuration protocol SECALARM Component for mapping security events on protocols such as...
  • Page 14 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v12 Table 3. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN,...
  • Page 15 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Table 4. Local HMI functions IEC 61850 or function ANSI Description name LHMICTRL Local HMI signals LANGUAGE Local human machine language SCREEN Local HMI Local human machine screen behavior FNKEYTY1–FNKEYTY5...
  • Page 16 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 The main purpose of the OOSPPAM function is to detect, words, operation is prioritized over strict adherence to evaluate, and take the required action during pole slipping preference.
  • Page 17 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 EF4PTOC can be set to be directional or non-directional No specific sensitive current input is needed. Sensitive independently for each step. directional residual overcurrent and power protection (SDEPSDE) can be set as low 0.25% of IBase.
  • Page 18 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Normally the own breaker is tripped to correct such a Two step residual overvoltage protection (ROV2PTOV) situation. If the situation persists the surrounding breakers function calculates the residual voltage from the three-phase should be tripped to clear the unsymmetrical load situation.
  • Page 19 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 SAPFRC is provided with an undervoltage blocking. The M12480-3 v16 The Synchronizing function allows closing of asynchronous operation is based on positive sequence voltage networks at the correct moment including the breaker closing measurement and requires two phase-phase or three phase- time, which improves the network stability.
  • Page 20 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 SEMOD55850-5 v7 Bay control QCBAY Generic communication function for Double Point indication M13447-3 v8 The Bay control (QCBAY) function is used together with Local (DPGAPC) function block is used to send double point...
  • Page 21 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 signal to the remote end, and to block the permissive tripping This is why the IEDs have available additions to the scheme at the local end. This blocking condition is maintained long communication logic.
  • Page 22 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 according to the specific application needs for settable pulse • SRMEMORY function block is a flip-flop that can set or or steady output. reset an output from two inputs respectively. Each block has two outputs where one is inverted.
  • Page 23 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 • Disturbance recorder Integer to Boolean 16 conversion with logic node • Fault locator representation ITBGAPC • Settings information SEMOD158421-5 v9 Integer to boolean conversion with logic node representation...
  • Page 24 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 The event recorder logs all selected binary input signals Analog, integer and double indication values are also connected to the Disturbance recorder function. Each transferred through the EVENT function.
  • Page 25 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 values. The pulses are captured by the binary input module Fault locator LMBRFLO and then read by the PCFCNT function. A scaled service M13970-3 v13 The accurate fault locator is an essential component to value is available over the station bus.
  • Page 26: Human Machine Interface

    1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M11345-3 v10 13. Human machine interface Precision time protocol PTP Local HMI PTP according to IEEE 1588-2008 and specifically its profile AMU0600442 v14 IEC/IEEE 61850-9-3 for power utility automation is a synchronization method that can be used to maintain a common time within a station.
  • Page 27: Station Communication

    Route from source to destination through gateway SPA communication protocol SEMOD120134-5 v1 A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation automation systems but the main use is for Substation 16.
  • Page 28: Hardware Description

    1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 CMD_OFF and CMD_ON, that can be used to implement Function status earth-fault for IEC 60870-5-103 I103EF double-point command schemes. I103EF is a function block with defined functions for earth fault indications in monitor direction.
  • Page 29 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Alternative connectors of Ring lug or Compression type can the measuring transformers. The module has twelve inputs in be ordered. different combinations of currents and voltage inputs. Binary input module BIM...
  • Page 30 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M15243-12 v9 IEC04000464-3-en.vsdx IEC04000464 V3 EN-US Figure 7. Case without rear cover with 19” rack mounting kit Case size (mm)/(inches) 6U, 1/2 x 19” 265.9/ 223.7/ 242.1/ 255.8/ 205.7/...
  • Page 31: Connection Diagrams

    1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 18. Connection diagrams Connection diagram, REL650 2.2, A12X00 1MRK006507-LB GUID-CF4EFFA5-3081-4FC7-9A14-ED127C3C0FDE v6 The connection diagrams are delivered in the IED Connectivity package as part of the product delivery. Connection diagrams for Customized products The latest versions of the connection diagrams can be Connection diagram, 650 series 2.2 IEC...
  • Page 32: Technical Data

    1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 19. Technical data General M10993-1 v3 IP11376-1 v2 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range...
  • Page 33 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Energizing quantities, rated values and limits Analog inputs M16988-1 v11 IP15842-1 v1 Table 5. TRM - Energizing quantities, rated values and limits for protection transformer Description Value Frequency...
  • Page 34 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Table 7. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20% 220/250 V RL ±20%...
  • Page 35 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M12573-1 v9 Table 9. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20%...
  • Page 36 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M12584-1 v7 Table 11. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
  • Page 37 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Table 13. Temperature and humidity influence Parameter Reference value Nominal range Influence Ambient temperature, operate +20°C -20°C to +55°C 0.02%/°C value Relative humidity 10-90% 10-90% Operative range 0-95% Storage temperature -40°C to +70°C...
  • Page 38 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Table 16. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV...
  • Page 39 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Table 18. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C...
  • Page 40 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Impedance protection GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v7 Table 21. Distance protection ZMFPDIS Function Range or value Accuracy Number of zones 3 selectable directions, 3 fixed directions Minimum operate current, Ph-Ph (5-6000)% of IBase ±1.0% of I...
  • Page 41 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M16036-1 v10 Table 22. Power swing detection ZMRPSB Function Range or value Accuracy Reactive reach ±2.0% static accuracy (0.10-3000.00) W/phase Conditions: Voltage range: (0.1-1.1) x U Current range: (0.5-30) x I...
  • Page 42 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 GUID-42119BFF-1756-431C-A5A1-0AB637213E96 v1 Table 25. Phase preference logic PPL2PHIZ Function Range or value Accuracy Operate value, phase-to-phase (1 - 100)% of UBase ±0.5% of U and phase-to-neutral undervoltage Reset ratio, undervoltage <...
  • Page 43 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Current protection M12336-1 v13 Table 27. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 44 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M12342-1 v20 Table 28. Directional phase overcurrent protection, four steps OC4PTOC Function Setting range Accuracy Operate current, step 1-4 (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 45 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M15223-1 v17 Table 30. Directional residual overcurrent protection, four steps EF4PTOC Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 46 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6 Table 31. Four step directional negative phase sequence overcurrent protection NS4PTOC Function Range or value Accuracy Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of I at I £...
  • Page 47 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 SEMOD173350-2 v16 Table 32. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of IBase Operate level for 3I ·cosj directional residual ±1.0% of I at I £...
  • Page 48 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M12352-1 v14 Table 33. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F...
  • Page 49 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M13279-1 v10 Table 35. Pole discordance protection CCPDSC Function Range or value Accuracy Operate current (0–100)% of IBase ±1.0% of I Independent time delay (0.000-60.000) s ±0.2% or ± 30 ms whichever is greater...
  • Page 50 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Voltage protection M13290-1 v15 Table 37. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U Absolute hysteresis (0.0–50.0)% of...
  • Page 51 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M13304-1 v14 Table 38. Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >...
  • Page 52 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M13317-2 v14 Table 39. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 - step 2 (1.0-200.0)% of UBase ± 0.5% of U at U ≤...
  • Page 53 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Frequency protection M13360-1 v15 Table 40. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function, at symmetrical three (35.00-75.00) Hz ±2.0 mHz phase voltage Operate time, start at f + 0.02 Hz to f...
  • Page 54 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M14976-1 v9 Table 42. Rate-of-change of frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz...
  • Page 55 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Secondary system supervision M12358-1 v10 Table 43. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I >...
  • Page 56 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Control M12359-1 v15 Table 45. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase...
  • Page 57 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M12379-1 v13 Table 46. Autorecloser SMBRREC Function Range or value Accuracy Dead time: shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms shot 1 “t1 2Ph” whichever is greater shot 1 “t1 3Ph “...
  • Page 58 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Scheme communication M16038-1 v14 Table 47. Scheme communication logic with delta based blocking scheme signal transmit ZCPSCH Function Range or value Accuracy Scheme type Intertrip Permissive UR Permissive OR...
  • Page 59 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 GUID-CC9A02C2-AAE8-4B8C-A091-D4ED584A2EA7 v1 Table 50. Local acceleration logic ZCLCPSCH Function Range or value Accuracy Operate current, LoadCurr (1–100)% of IBase ±1.0% of I Operate current, MinCurr (1–100)% of IBase ±1.0% of I...
  • Page 60 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Logic M12380-1 v12 Table 52. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s...
  • Page 61 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v2 Table 59. Number of AND instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v2 Table 60. Number of GATE instances...
  • Page 62 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 GUID-C6C98FE0-F559-45EE-B853-464516775417 v2 Table 67. Number of TIMERSET instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms TIMERSET (0.000–90000.000) s ±0.5% ±10 ms GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v1 Table 68.
  • Page 63 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Table 74. Number of TEIGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms TEIGAPC GUID-CEA332FF-838D-42B7-AEFC-C1E87809825E v2 Table 75. Number of INTCOMP instances Function Quantity with cycle time...
  • Page 64 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Monitoring M12386-1 v15 Table 77. Power system measurement CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U≤ 50 V ±0.2% of U at U>...
  • Page 65 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6 Table 80. Voltage measurement phase-earth VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V...
  • Page 66 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M12760-1 v10 Table 84. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings...
  • Page 67 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v7 Table 86. Insulation supervision for liquid medium function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value Oil lockout level 1.00-100.00 ±10.0% of set value...
  • Page 68 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M13765-1 v5 Table 90. Indications Function Value Buffer capacity Maximum number of indications presented for single disturbance Maximum number of recorded disturbances M12702-1 v4 Table 91. Event recorder...
  • Page 69 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Metering M13404-2 v5 Table 96. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value SEMOD153707-2 v5 Table 97.
  • Page 70 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Station communication M15031-1 v8 Table 98. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0...
  • Page 71 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 M12589-1 v4 Table 103. SLM – LON port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *)
  • Page 72 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Hardware M11778-1 v6 SEMOD53385-1 v1 Table 107. Case Material Steel sheet Front plate Stainless steel with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v4 Table 108.
  • Page 73 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v2 Table 114. NUM: Communication ports 4 Ethernet ports 1 Basic, 3 Optional Ethernet connection type SFP Optical LC or Galvanic RJ45...
  • Page 74 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Basic IED functions M11963-1 v5 Table 115. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v8 Table 116.
  • Page 75 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Inverse characteristic M12388-1 v21 Table 119. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 ANSI/IEEE C37.112 , 1.5 x I ≤...
  • Page 76 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Table 120. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is...
  • Page 77 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v3 Table 122. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 2.00 ANSI/IEEE C37.112 ,...
  • Page 78 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Table 123. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 2.00 IEC 60255-151, ±5.0% 1.5 x I...
  • Page 79 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v1 Table 125. ANSI Inverse time characteristics for Voltage restrained time overcurrent protection Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 ANSI/IEEE C37.112 , ±...
  • Page 80 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 SEMOD116978-2 v10 Table 127. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 81 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Table 128. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 82 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Table 129. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of ±5.0% or ±45 ms whichever is greater 0.01...
  • Page 83: Ordering For Pre-Configured Ied

    To obtain the complete ordering code, please combine code from the tables, as given in the example below. Example code: REL650*2.2-A11X00- P23-B1A12-AA-CA-B-A3-CD1AX-KXXXXXLXGX. Using the code of each position #1-11 specified as REL650*1-2 2-3-4 4-5 6-7 7-8-9 9-10 10 10 -11 11 11...
  • Page 84 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Mounting details with IP40 of protection from the front Ordering no Notes and rules No mounting kit included 19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12 1MRK002420-BB 19"...
  • Page 85 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Binary input/output modules Ordering no Notes and rules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1 BIM required in position P3 and 1 BOM always included in position P4.
  • Page 86: Ordering For Accessories

    1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 21. Ordering for Accessories Accessories IP15151-1 v1 Interface converter (for remote end data communication) M16668-3 v9 External interface converter from C37.94 to G703 Quantity: 1MRK 002 245-AA External interface converter from C37.94 to G703.E1...
  • Page 87 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Rule: Specify additional quantity of IED Connect USB flash drive requested . Quantity: 1MRK 003 500-AB User documentation Rule: Specify the number of printed manuals requested Application manual...
  • Page 88 1MRK 506 384-BEN A Line distance protection REL650 2.2 Product version: 2.2.1 Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name: Voltage level:...
  • Page 90 — ABB AB Grid Automation Products 721 59 Västerås, Sweden Phone: +46 (0) 21 32 50 00 abb.com/protection-control © Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice.