hit counter script

Testing The Liquid Medium Supervision For Level Alarm And Level Lockout Conditions; Testing The Liquid Medium Supervision For Temperature Alarm And Temperature Lock Out Conditions; Completing The Test - ABB REG670 Commissioning Manual

Generator protection, relion 670 series
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 13
Testing functionality by secondary injection
13.12.2.1
13.12.2.2
13.12.2.3
256
Check that the input logical signal BLOCK is logical zero and that on the local
HMI, the logical signals LVLALM, LVLLO, TEMPALM, TEMPLO, ALARM and
LOCKOUT are logical zero.
Testing the liquid medium supervision for level alarm and level
lockout conditions
1.
Connect the binary inputs to consider liquid level to initiate the alarms.
2.
Consider the analogue level input SENLEVEL and set SENLEVEL to a value
lower than LevelAlmLimit or activate binary input signal SENLVLALM, check
that outputs LVLALM and ALARM are activated after a set time delay of
tLevelAlarm.
3.
Liquid level lockout input SENLVLLO can be used to set LVLLO.
4.
Also, reduce the liquid level input below LevelLOLimit or activate the binary
input signal SENLVLLO, check that LVLLO signal after a set time delay of
tLevelLockOut.
5.
Activate BLOCK binary input and check that the outputs LVLALM, LVLLO,
ALARM and LOCKOUT disappears.
6.
Reset the BLOCK binary input.
7.
Make sure that level lockout condition exists and then activate the reset lock
out input RESETLO and check that the outputs PRESLO and LOCKOUT reset.
Testing the liquid medium supervision for temperature alarm and
temperature lock out conditions
1.
Consider the analogue temperature input SENTEMP and set SENTEMP to a
value higher than TempAlarmLimit, check that outputs TEMPALM and ALARM
are activated after a set time delay of tTempAlarm.
2.
Temperature lockout input SETTLO can be used to set TEMPLO signal.
3.
Also, increase further the temperature input above TempLOLimit, check that
the outputs TEMPLO and LOCKOUT appears after a set time delay of
tTempLockOut.
4.
Activate BLOCK binary input and check that the outputs TEMPALM, TEMPLO,
ALARM and LOCKOUT disappear.
5.
Reset the BLOCK binary input.
6.
Make sure that temperature lockout condition exists and then activate the
reset lock out input RESETLO and check that the outputs TEMPLO and
LOCKOUT reset.

Completing the test

Continue to test another function or end the test by changing the TestMode setting
to Off. Restore connections and settings to their original values, if they were
changed for testing purposes.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 073-UEN A
GUID-C1F1E6CA-9512-4358-A4E7-84CC3698D156 v3
GUID-189AF20B-D0E3-453D-A787-68F25D0903D3 v1
GUID-1A0D8AF0-4C48-45E8-B31D-96734ED1A4D2 v1
Commissioning manual

Advertisement

Table of Contents
loading

Table of Contents