Contact Siemens customer service for EDS files.
5.5.8
Network Status Detection Setup
An SOP flag is available to show the network status:
● For network 1: Network1CommOk_I
● For network 2: Network2CommOk_I
The SOP flag is set to "1" (true) when the network connection is operating normally, and "0"
(false) when it is not operating normally.
The network status is automatically detected. The detection time takes approximately
20 - 40 milliseconds. If a longer time-out period is desired for a network that automatically
detects the network status, it must be implented through SOP Logic.
5.5.9
Network Setup Procedure
Note
Setup functions are contained in the Configure Parameters Menu (9902), which is a submenu
of the Communications Menu (9).
Access is security-controlled at level 7; you must enter the security code to access these
parameters.
Refer to the
levels and codes.
Use the following procedure to complete network setup. Refer to Table
Menu (9902) in Section Parameter Assignment/Addressing for the menus needed to complete
setup.
Procedure
1. Select a protocol using parameter 'Network 1 Type' (9901). Scroll to "Ethernet/IP" and press
[ENTER]. The configuration parameters are viewable.
2. Set parameter 'Velocity Units' (9080) to the desired motor speed units for motor
commanded speed and motor feedback speed scaling.
3. Where necessary, set parameter 'Demand Scalar' (9912) to:
n x command speed where –125 % to 125 %
4. Set parameter 'Aux Demand Scalar' (9913) if used.
NXGpro Communication
Function Manual, AB, A5E33486415A
NXGpro Control Operating Manual for further information on security access
Ethernet / IP Communication
5.5 Planning/Configuring
Configure Parameters
131