ON/OFF control
Note:
Setting the sequence and the control outputs
Application for
chilled / heated ceiling, radiator
Chilled / heated ceiling with
changeover
Chilled / heated ceiling & el heater
(cooling only: disable el heater
via P13)
Chilled ceiling and radiator
42 / 94
Siemens
Building Technologies
The diagrams below show the control sequence for 2-position control.
Heating mode with manual selection
(P01 = 2)
Y1
Y
1
w
0
½ SDH
½ SDH
Heating and cooling mode (P01 = 04)
Y
Y1
x
x
½
½
dz
dz
1
w
0
½ SDC
½ SDH
½ SDH
∂ The diagrams only show the PI thermostat's proportional part.
∂ For the fan sequence see section 3.8.
Refer to section 3.4, section 3.6.1, and section 3.7.
3.6.6
Chilled / heated ceiling and radiator applications*
For chilled / heated ceiling and radiator,
∂ set the corresponding basic application
∂ disable the fan (P52)
The following applications are available:
* Not applicable for RDF301 and RDF301.50.
RDF301, RDF301.50..., RDF600KN, RDF600KN/S
Cooling mode with manual selection
(P01 = 2)
Y
1
T[°C]
0
½ SDC
T[°C] Room temperature
Y2
w
Y1
Y2
SDH Switching differential "Heating" (P30)
T[°C]
½ SDC
SDC Switching differential "Cooling" (P31)
X
dz
Set basic application
2-pipe
2-pipe and electric heater
4-pipe
Basic Documentation
Y2
w
T[°C]
½ SDC
Room temperature setpoint
Control command "Valve" or "Comp." (H)
Control command "Valve" or "Comp." (C)
Dead zone (P33)
See
Sequences
section
H
3.6.3
C
El H + H (
3.6.4
El H + C (
C
H + C
3.6.5
( \ )
( / )
\ \ )
6
\ / )
6
( / )
( \ / )