Installation Instructions
Model HCP
Intelligent Control Point
INTRODUCTION

PROGRAMMING

P/N 315-034860-13
The Model HCP Intelligent Control Point from Siemens
Industry, Inc. provides remote, independent control of
any of the following:
1. A notification appliance circuit (NAC)
2. A telephone zone (XLS only)
3. A speaker zone (25V or 70.7V RMS) (XLS only,
FV2025/2050, FV922/924)
The HCP communicates through the DLC device loop
card of the FireFinder-XLS System, the FS-DLC device
loop card of the FS-250 System, the FC922/FV922,
FC2025/FV2025 periphery FCI2016 Board (250p)
detector circuits, and the FC2050/FV2050, FC924/FV924
FCI2017 periphery board (500p) detector circuits. Each HCP
uses one device address on the device loop.
Use the DPU Programmer/Tester to program and test the module.
The HCP may only be assigned addresses 1 to 60. It is recommended to program
the HCP devices first to ensure that enough addresses have been reserved for them.
Other devices may then be assigned to addresses in this range that were not
assigned to an HCP .
Disconnect wire at terminal 1 and 2 on TB1 before programming.
To set the HCP device address:
Plug the programming cable of the DPU Programmer/Tester into the two-
pin programming points on the HCP . (See Figure 1 for location.)
Set the device address for the HCP by following the instructions in the DPU
Programmer/Tester Manual, P/N 315-033260.
Each HCP can be assigned a custom message using either the Zeus Programming Tool
(XLS System), the FS-CT2 (FS-250 System), the FC2025/2050, FV2025/2050 FSX2002
Engineering Tool, or the FC922/924, FV922/924 FSX7212 Engineering Tool. Refer to
the Zeus Quick Start Manual, P/N 315-033875, or the FS-250 Programming Manual, P/
N 315-049403, as applicable.
PROGRAMMING
POINTS
Figure 1

HCP Intelligent Control Point

Siemens
Siemens
Industry
Industry
Industry, , , , , Inc.
Siemens Industry
Siemens
Siemens
Industry
Building
Building
Building
Building T T T T T ec
Building
ec
ec
echnologies Di
ec
hnologies Di
hnologies Di
hnologies Division
hnologies Di
Inc.
Inc.
Inc.
Inc.
vision
vision
vision
vision

Advertisement

Table of Contents
loading

Summary of Contents for Siemens HCP

  • Page 1 PROGRAMMING Use the DPU Programmer/Tester to program and test the module. The HCP may only be assigned addresses 1 to 60. It is recommended to program the HCP devices first to ensure that enough addresses have been reserved for them.
  • Page 2 PSX-12, and PAD-4. Wiring should be connected to TB3 on the PSC-12 and PSX-12, or the auxiliary power supply on the PAD-4. For FS-250 Systems, the HCP is powered by the NAC circuits and PAD-4. Wiring should be connected to the NAC circuits on the main board or the auxiliary power supply on the PAD-4.
  • Page 3 NEC 760. 5. All wiring must conform to national and local electrical codes. X1401/X1402 X1401/X1402 X1801/X1802 X1801/X1802 Detector circuits on periphery board for FC922/FV922, FC2025/FV2025 Figure 3 FS20 Device Loop Connections Siemens Industry, Inc. P/N 315-034860-13 Building Technologies Division...
  • Page 4 See the HCP Power Supply section (above) for compatible power sources. The maximum output load that may be connected to an HCP is 1.5A at 24 VDC. If the 24 VDC is lost or the NAC line is broken or shorted while the HCP is in supervisory mode, a...
  • Page 5 The common talk riser connects continuously to each HCP with a 10K end of line device at the last HCP . Tie the shield of these riser wires together using terminal 5 of TB2 and isolate them from the system circuits and the earth ground.
  • Page 6 PMI/PMI-2 of the FireFinder-XLS. The 70.7V/25V RMS audio input to the HCP must be power limited, such as from the ZAC-40. The ZAC-40 supervises the audio connection path to the HCP and provides up to 40 watts of power.
  • Page 7 VCI2001-U1 Amplifier Card. The VCI2001-U1 supervises the audio connection path to the HCP and provides up to 50 watts of power. The VCI2001-U1 can be wired Style Y (Class B) or Style Z (Class A). Refer to the VCI2001-U1 Installation Instructions, Document ID A6V10370410, for further information.
  • Page 8 Siemens Industry, Inc. P/N 315-034860-13 Building Technologies Division...
  • Page 9 Siemens Industry, Inc. P/N 315-034860-13 Building Technologies Division...
  • Page 10 Siemens Industry, Inc. P/N 315-034860-13 Building Technologies Division...
  • Page 11 Mounting Be sure to program the HCP before mounting the unit to the switchbox. (Refer to PROGRAMMING on page 1.) The HCP should be installed in a UL listed electrical box. (See Figure 12.) Use a standard 3 -inch deep, double gang electrical switchbox or a 4-inch...
  • Page 12 Cyber security disclaimer Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept.

Table of Contents