hit counter script
Download Print this page
Siemens HTRI-M Installation Instructions

Siemens HTRI-M Installation Instructions

Addressable interface module

Advertisement

Quick Links

Installation Instructions
Model HTRI-M
Addressable Interface Module
PROGRAMMING
P/N 315-049480-4
The Model HTRI-M Series Addressable Interface
Module from Siemens Industry, Inc. interfaces
direct shorting devices to the DLC loop circuit of
the FireFinder-XLS System or the FS-DLC loop of
the FS-250 System. It is also approved for 1076,
Proprietary Burglary.
The HTRI-M can monitor a normally open or closed
dry contact and it can report the status of the contact.
Refer to Figure 1 to locate the red and black DLC/FS-DLC loop circuit wires of the HTRI-M.
Connect the Addressable Loop Driver circuit wires of the HTRI-M to the Model DPU
Programmer/Tester. Use the cable provided with the Programmer/Tester and the 2
alligator clip to banana plug adapters provided.
To Prevent Damage To The DPU:
DO NOT connect a HTRI-M to the DPU until all field wiring is removed from the
red and black DLC/FS-DLC loop circuit wires of the HTRI-M.
Connection from the DPU to the HTRI-M is not polarity sensitive. Refer to Figure
3 for the proper connections to the control panel.
(Refer to Figure 2.) Follow the instructions in the DPU Programmer/Tester Manual
(P/N 315-033260) to program the desired address into HTRI-M.
Record the device address on the label located on the HTRI-M. The HTRI-M can now
be installed and wired to the system.
NORMALLY CLOSED
PROGRAMMABLE
(SEE NOTE 4)
END OF LINE
RESISTOR
470 OHMS,
1/4W
NOTES:
1. There can be any number of normally closed or normally open switches.
2. The end of line resistor must be located at the last switch.
3. Do not wire a normally closed switch across the end of line resistor.
4. Only for use with security and status applications.
5. Do not use N.O. switches for security applications.
Figure 2
Wiring Switches
SWITCHES
NORMALLY OPEN
Building
Building
Building T T T T T ec
Building
Building
Figure 1
HTRI-M Module
PROGRAMMABLE
SWITCHES
(SEE NOTES 2, 3 AND 5)
END OF LINE
RESISTOR
470 OHMS,
1/4W
Siemens
Siemens
Siemens Industry
Industry
Industry, , , , , Inc.
Industry
Siemens
Siemens
Industry
ec
ec
echnologies Di
ec
hnologies Di
hnologies Division
hnologies Di
hnologies Di
vision
vision
vision
vision
Inc.
Inc.
Inc.
Inc.

Advertisement

loading

Summary of Contents for Siemens HTRI-M

  • Page 1 HTRI-M Module PROGRAMMING Refer to Figure 1 to locate the red and black DLC/FS-DLC loop circuit wires of the HTRI-M. Connect the Addressable Loop Driver circuit wires of the HTRI-M to the Model DPU Programmer/Tester. Use the cable provided with the Programmer/Tester and the 2 alligator clip to banana plug adapters provided.
  • Page 2 6. For proprietary burglary application: a. Use a TSW-1/2 tamper switch to monitor the main enclosure. b. Monitor each HTRI-M related to this application continuously by using a listed motion detector (to prevent tampering). 7 . In supervisory: HTRI-M draws 1.3mA 8.