Page 1
The technical information in this manual is provided to explain the principal functions and applications of the product, but not to grant you a license to use the intellectual property or any other property of Toshiba Schneider Inverter Corporation or a third party.
E6581327 1. Introduction Thank you for your purchase of the Toshiba inverter “TOSVERT VF-AS1”. This instruction manual explains the light-load high-speed operation of VF-AS1. 2. Function The light-load high-speed operation is used to increase the operating efficiency of the machine by increasing the rotational speed of the motor when it is operated under light load.
E6581327 3. Related parameters Related parameters for light-load high-speed operation Minimum Vector control Commu Write Adjust Default setting unit Title nication Function Adjustment range during ment Speed Torque setting control control (Panel/Com running (Note) control control munication) 0:Deselect 1: High-speed operation speed set automatically (Power running at F command :Raising)
E6581327 4. Light-load high-speed operation Mode description The light-load high-speed operation includes the modes below: Each mode can be set by the light-load high-speed operation selection (f328). Title/function Default setting Action 0:Deselect Light-load high-speed operation disabled. 1:High-speed operation speed set automatically When inverter judges to be light-load, the (Power running at F command:Raising)
E6581327 4.1.1. Automatic setting mode of high-speed operation speed (f328=1, 2) The diagram on the next page(Fig.1) is the timing chart when the automatic setting mode of high-speed operation speed (f328=1) is applied to lift application. At the operation frequency above the light-load high-speed operation switching lower limit frequency (f331) (point A in the Fig.1), if a detected torque (*1) after completion of speed reach is below the switching load torque during power running (f335 setting value), the inverter judges to be light-load.
Page 7
E6581327 《Example of operation》Light-load high-speed operation selection (f328=1: High-speed operation speed set automatically): F (Raising) Light-load high-speed operation Operation frequency (Hz) High-speed operation frequency varies with load torque. f102 Light-load high-speed operation load detection time f333 Speed reach detection band Light-load high-speed operation load f102 detection waiting time f332...
E6581327 4.1.2. Fixed setting mode of high-speed operation speed (f328=3, 4) The diagram on the next page(Fig.2) is the timing chart when fixed setting mode of the high-speed operation speed(f328=3) is applied to lift application. At the operation frequency above the light-load high-speed operation switching lower limit frequency (f331) (point A in the Fig.2), if an average torque during the light-load high-speed operation load detection time (f333) after completion of speed reach and after the light-load high-speed operation load detection waiting time (f332) has elapsed is below the switching load torque during power running...
Page 9
E6581327 《Example of operation》 Light-load high-speed operation selection (f328=3: High-speed operation set with f330): F (Raising) Light-load high-speed operation Automatic light-load high-speed operation frequency f330 f102 Light-load high-speed operation Speed reach load detection time f333 detection band Light-load high-speed operation f102 load detection waiting time f332 Speed reach...
E6581327 5. How to adjust parameters If the light-load high-speed operation is used, it is necessary to always set the motor-related parameters (Motor constants) regardless of setting of V/f control mode selection (pt). Refer to Section 6-22 of VF-AS1 instruction manual (E6581301) to set motor-related parameters. In addition, for the high-speed operation fixed setting mode (f328=3, 4), the learning action allows the light-load high-speed operation to be adjusted easily.
E6581327 Fixed setting mode of high-speed operation speed 《Adjustment method using the learning function for lift application》 If the light-load high-speed operation is carried out with 60Hz of normal operation, follow the procedure below: ① Set the automatic light-load high-speed operation frequency (f330). Ex.: f330=90Hz ②...