hit counter script

Information List - Siemens SIPROTEC 4 Manual

Voltage and frequency protection
Hide thumbs Also See for SIPROTEC 4:
Table of Contents

Advertisement

Addr.
Parameter
5412
81-4 PICKUP
5413
81-4 PICKUP
5414
81-4 DELAY
5415A
DO differential
5421
FCT 81-1 O/U
5422
FCT 81-2 O/U
5423
FCT 81-3 O/U
5424
FCT 81-4 O/U

Information List

2.3.4
No.
Information
5203
>BLOCK 81O/U
5206
>BLOCK 81-1
5207
>BLOCK 81-2
5208
>BLOCK 81-3
5209
>BLOCK 81-4
5211
81 OFF
5212
81 BLOCKED
5213
81 ACTIVE
5214
81 Under V Blk
5232
81-1 picked up
5233
81-2 picked up
5234
81-3 picked up
5235
81-4 picked up
5236
81-1 TRIP
5237
81-2 TRIP
5238
81-3 TRIP
5239
81-4 TRIP
SIPROTEC 4, 7RW80, Manual
C53000-G1140-C233-4, Edition 07.2018
Setting Options
40.00 .. 60.00 Hz
50.00 .. 70.00 Hz
0.00 .. 100.00 sec
0.02 .. 1.00 Hz
OFF
ON f>
ON f<
OFF
ON f>
ON f<
OFF
ON f>
ON f<
OFF
ON f>
ON f<
Type of
Comments
Informa-
tion
SP
>BLOCK 81O/U
SP
>BLOCK 81-1
SP
>BLOCK 81-2
SP
>BLOCK 81-3
SP
>BLOCK 81-4
OUT
81 OFF
OUT
81 BLOCKED
OUT
81 ACTIVE
OUT
81 Under Voltage Block
OUT
81-1 picked up
OUT
81-2 picked up
OUT
81-3 picked up
OUT
81-4 picked up
OUT
81-1 TRIP
OUT
81-2 TRIP
OUT
81-3 TRIP
OUT
81-4 TRIP
Default Setting
Comments
51.00 Hz
81-4 Pickup
61.00 Hz
81-4 Pickup
30.00 sec
81-4 Time delay
0.02 Hz
Dropout differential
OFF
81-1 Over/Under Frequency
Protection
OFF
81-2 Over/Under Frequency
Protection
OFF
81-3 Over/Under Frequency
Protection
OFF
81-4 Over/Under Frequency
Protection
Functions
2.3 Frequency Protection 81 O/U
49

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7rw80

Table of Contents