5.35.2 Fitting the EVAC-NL mimic display driver FT2003-N1
Building Technologies
Fire Safety
1. Mount the operating add-on FCM2008-N1 (5) on the Eco housing (2) or on any
housing.
2. If the power supply is integrated, install power supply (3) in the Eco
housing (2).
3. Depending on the number of zones, mount 1 or 2 EVAC-NL connector boards
FTI2002-N1 (1, 4) with spacer bolts in the housing (2).
4. Wire up the power supply, connector boards and the operating add-on
according to the following pin assignments.
5. Check the address settings on the EVAC-NL operating units FTO2007-N1 with
the following address setting.
6. Swivel the operating add-on (5) on to the housing (2), secure it, and fit the
cover cap (for Eco housing).
5
X3
4
X1
3
Figure 124: Assembly of EVAC-NL mimic display driver FT2003-N1
1
EVAC-NL operating unit FTO2007-N1
2
Ribbon cable between EVAC-NL connector board and EVAC-NL
operating unit
3
EVAC-NL connector board FTI2002-N1
4
4 spacer bolts (15 mm) and fixing screws for securing housing
5
4 spacer bolts (15 mm) and fixing screws for fixing printed circuit board
X1/
Connection strip for supply, monitoring signals and RS485 connection
FTI2002
X2
Connections of LED mimic display indicator 1...17
Mounting and installation of the compact control panels
Remote EVAC-NL and EVAC-NL mimic display driver
X2
X1
X402
2
X4
X5
008851_s_en_--
5
1
X400
229 | 354
2016-01-27