Turn on Web Server
Note
16 / 143
Siemens
Building Technologies
2.2
Getting started
2.2.1
Turn on Web Server
Connect the Web Server to the power supply and connect it to the PC:
1. Connect power supply to turn on power on Web Server. The Web Server is
operational, when the green
2. Check additional displays:
· LED A
Green light if LPB/BSB bus power supply is available. Check the LPB/BSB
bus wiring and setting for the bus power supply on the bus device if no bus
power supply is available.
· LED
Dark if no fault is pending. You can resolve pending faults later (see
Section 2.9).
3. Plug the supplied USB cable into the Web Server and the PC and start up the
PC. The PX recognizes the Web Server as a USB device. Otherwise, the
RNDIS is still not installed.
4. The RNDIS driver is installed automatically if the PC is connected to the
Internet and no RNDIS driver is installed. The installation wizard will guide you
through installation.
You can also manually set up the RNDIS driver (see Section 9.3.3).
Web Server OZW672... V6.0
Commissioning
LED is lit.
CE1C5712en
2015-10-13