Supplemental information on AI 8 x 13-bit

Unused channels
Set the "disabled" value at the "measurement type" parameter for unused channels. This
setting reduces module cycle times.
Interconnect the M- terminals of unused channels.
Using PTC resistors
PTCs are suitable for monitoring the temperature of or providing thermal protection for complex
drives and transformer windings. The module has no analog values when PTC resistances are
used. Status information on fixed temperature ranges are displyed instead of analog values.
● When setting the parameters, select measurement type R "Resistance" and measuring
range "PTC".
● Connect the PTC (see "Terminal diagram for resistance measurement").
● Use PTC resistors that comply with IEC 60034-11-2 (previously, PTC thermistors that
complied with DIN/VDE 0660, Part 302).
● Sensor data for the PTC resistor:
Switching points
(RRT-5) °C
(RRT+5) °C
(RRT+15) °C
Measurement volt‐
age
Voltage at PTC
ET 200PA SMART
Operating Instructions, 06/2019, A5E34192013-AB
Property
Technical specifica‐
tions
Response to rising temperature
< 550 Ω
550 Ω to 1650 Ω
> 1650 Ω
Response to falling temperature
> 750 Ω
750 Ω to 540 Ω
< 540 Ω
Max. 550 Ω
Min. 1,330 Ω
Min. 4,000 Ω
Max. 7.5 V
ET 200PA SMART I/O modules
Comment
Normal range:
Bit 0 = "0", bit 2 = "0" (in the PII)
Advance warning range:
Bit 0 = "0", bit 2 = "1" (in the PII)
Actuating range:
Bit 0 = "1", bit 2 = "0" (in the PII)
Actuating range:
Bit 0 = "1", bit 2 = "0" (in the PII)
Advance warning range:
Bit 0 = "0", bit 2 = "1" (in the PII)
Normal range:
Bit 0 = "0", bit 2 = "0" (in the PII)
RRT = Rated response temperature
10.4 Analog input modules
163