Siemens SINAMICS G120 Installation Manual page 63

Power modules, ip20 / push-through technology (pt)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Additional information when connecting FSG converters
Note
Conductor cross-section 240 mm
Cable lugs for M10 bolts according to SN71322 are suitable for cables with cross-sections of
35 mm
If you wish to establish connections with cables of 240 mm
narrow cable lugs, e.g. Klauke 12SG10. Other cable lugs are not suitable due to the narrow
design of the converter.
The maximum permissible width of the cable lugs is 37 mm (1.45 inches).
Remove the plastic insulating plate as shown below to gain better access to the terminals for
the power connections.
Damage to converter as a result of operation without insulating plates
Without the insulating plates, voltage flashovers may occur between the phases.
• Replace the insulating plates after connecting the cables.
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
... 185 mm
(1 AWG ... 2 × 350 MCM).
2
2
WARNING
4.2 Connecting the line and motor cable at the converter
2
(500 MCM), you must use
2
Connecting
61