hit counter script

Siemens SINAMICS G120 Installation Manual page 97

Power modules, ip20 / push-through technology (pt)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Table 6- 26
PM240-2, PT, frame size E, 380 V ... 480 V 3 AC
Article No. without filter
Article No. with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Approx. 1.4 kW through the heatsink
1)
Table 6- 27
PM240-2, IP20, frame size F, 380 V ... 480 V 3 AC
Article No. without filter
Article No. with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
6SL3211-1PE31-1UL0
6SL3211-1PE31-1AL0
55 kW
104 A
110 A
45 kW
94 A
90 A
3NA3836 (160 A)
150 A
1.65 kW
1)
1.67 kW
1)
83 l/s
30.5 kg
32 kg
6SL3210-1PE31-5UL0
6SL3210-1PE31-5AL0
75 kW
140 A
145 A
55 kW
117 A
110 A
3NA3140 (200 A)
200 A
1.91 kW
1.93 kW
153 l/s
58 kg
64 kg
6SL3210-1PE31-8UL0
6SL3210-1PE31-8AL0
90 kW
172 A
178 A
75 kW
154 A
145 A
3NA3142 (224 A)
250 A
2.46 kW
2.48 kW
153 l/s
58 kg
64 kg
Technical data
6.5 400 V converters
6SL3210-1PE32-1UL0
6SL3210-1PE32-1AL0
110 kW
198 A
205 A
90 kW
189 A
178 A
3NA3250 (300 A)
300 A
2.28 kW
2.30 kW
153 l/s
62 kg
66 kg
95

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics pm240-2

Table of Contents

Save PDF