O Extension Module 1 - ABB ACS880 PCP Firmware Manual

Control program
Table of Contents

Advertisement

No.
Name/Value
13.28
AO2 source max
-32768.0...32767.0
13.29
AO2 out at AO2 src
min
0.000...22.000 mA
13.30
AO2 out at AO2 src
max
0.000...22.000 mA
13.91
AO1 data storage
-327.68 ... 327.67
13.92
AO2 data storage
-327.68 ... 327.67
14
14 I/O extension module
1
14.01
Module 1 type
None
FIO-01
FIO-11
FAIO-01
14.02
Module 1 location
Slot 1
Slot 2
Slot 3
4...254
Description
Defines the real maximum value of the signal (selected by
parameter
13.22 AO2
source) that corresponds to the
maximum required AO2 output value (defined by
parameter
13.30 AO2 out at AO2 src
13.27 AO2 source
min.
Real signal value corresponding to maximum AO2 output
value.
Defines the minimum output value for analog output AO2.
See also drawing at parameter
Minimum AO2 output value.
Defines the maximum output value for analog output AO2.
See also drawing at parameter
Maximum AO2 output value.
Storage parameter for controlling analog output AO1 eg.
through fieldbus.
In
13.12 AO1
source, select
this parameter as the target of the incoming value data.
With the embedded fieldbus interface, simply set the target
selection parameter of that particular data to
storage.
Storage parameter for AO1.
Storage parameter for controlling analog output AO2 eg.
through fieldbus.
In
13.22 AO2
source, select
this parameter as the target of the incoming value data.
With the embedded fieldbus interface, simply set the target
selection parameter of that particular data to
storage.
Storage parameter for AO2.
Configuration of I/O extension module 1.
See also section
Programmable I/O extensions
Note: The contents of the parameter group vary according
to the selected I/O extension module type.
Activates (and specifies the type of) I/O extension module
1.
Inactive.
FIO-01.
FIO-11.
FAIO-01.
Specifies the slot (1...3) on the control unit of the drive into
which the I/O extension module is installed. Alternatively,
specifies the node ID of the slot on an FEA-0x extension
adapter.
Slot 1.
Slot 2.
Slot 3.
Node ID of the slot on the FEA-0x extension adapter.
max). See parameter
13.27 AO2 source
min.
13.27 AO2 source
min.
AO1 data
storage. Then set
AO1 data
AO2 data
storage. Then set
AO2 data
(page 56).
Parameters 149
Def/
FbEq16
100.0
1 = 1
0.000 mA
1000 = 1 mA
20.000 mA
1000 = 1 mA
0.00
100 = 1
0.00
100 = 1
None
0
1
2
4
Slot 1
1
2
3
1 = 1