Section 2: System Installation; Standard System Components - YZ Systems NJEX 7300G Instructions & Operating Manual

Natural gas odorization system
Hide thumbs Also See for NJEX 7300G:
Table of Contents

Advertisement

Section 2: System Installation

Section 2: System Installation

Standard System Components

Standard primary components of the NJEX-7300G
include the following:
• System Enclosure, figure 1. Houses the Model
7000F pump, the Model VM-1100 Verometer, the
odorant fill valve, the solenoid valve/pneumatic
relay manifold, the odorant discharge manifold, the
system control enclosure, *power supply enclosure,
and bulk odorant filter.
• *SPS12 Solar Panel Assembly, figure 1. The stan-
dard solar panel for the 7300G is equipped with a
mounting bracket and a connection cable.Optional
LPS-120/240 may be used in lieu of the solar panel.
• System Control Enclosure. Houses the N-300G
controller. (Not illustrated)
• *Power Supply Enclosure. Houses the battery, char-
ger supply, and I.S. Barrier. (Not illustrated)
• Bulk Odorant Filter, figure 3. Provides primary
odorant filtration between the storage tank and
the NJEX-7300G. The Bulk Odorant Filter is pre-
installed inside the System Enclosure attachment to
the odorant source is via an odorant inlet manifold
equipped with 1/4" FNPT connection located on the
back of the System Enclosure.
• Service Tray, (Not Illustrated), should be installed in
the bottom of the system enclosure, to capture any
drops that may occur during servicing of the odor-
izer.
• Mechanical Cabinet Cable, figure 3. Provides the
connection between the system control enclosure
and the electrical components in the mechanical
section.
• Expansion Tank, figure 2. Provides a closed loop
system for pressure fluctuations within the Verom-
eter during the odorant fill/injection cycle.
• NJEX Gas Filter, figure 2. Installed between the
actuation gas regulator and the actuation gas mani-
folds, this filter provides a 25 micron coalescent
filtration to insure a clean pneumatic supply.
• Actuation Gas Regulator, figure 3. Provides addi-
tional regulation of supply gas to actuate the pump.
Y Z S y s t e m s M i l t o n R o y • 2 0 1 I v y l a n d R o a d • I v y l a n d , P e n n s y l v a n i a • U S A • 1 8 9 7 4 • P : 2 8 1 . 3 6 2 . 6 5 0 0 • w w w. y z s y s t e m s . c o m
NJEX 7300G ver.08-2018
• SPS12 Solar Panel Assembly
System Enclosure
Figure 1
Actuation Gas Regulator
Figure 3
* ATEX installations refer to Appendix E. page 117.
Expansion
Tank
NJEX Gas
Filter
Figure 2
Bulk Odorant Filter
Page 5