hit counter script

Manual Control; Simulations; Telephone Customer Service; Input / Output Test - Siemens Albatros 2 RVS13 Series User Manual

Boiler controllers
Table of Contents

Advertisement

Manual control

Setpoint adjustment with
manual control

simulations

Telephone customer service

82/109
Siemens
Building Technologies
Line no.
Operating line
7140
Manual control
When manual control is activated, the relay outputs are no longer energized and
deenergized according to the control state but are set to a predefined manual control
state in accordance with their functions (see table below).
The burner relay energized in manual control can be deenergized by the electronic
temperature controller (TR).
Marking
Oil / gas boiler
Burner 1st stage
boiler pump
Bypass pump
Solar
Collector pump
DHW
charging pump
Diverting valve
circulating pump
electric immersion heater
Heating circuits 1...3
Heating circuit pump
Mixing valve opening /
Heating circuit pump 2nd
extra functions
pump H1
Pump H2
alarm output
After manual control has been activated, a change to the basic display must be made.
There, the maintenance/special mode symbol
Press the Info button to switch to info display "Manual mode", where the setpoint can
be adjusted.
Line no.
Operating line
7150
Simulation outside temp
To facilitate commissioning and fault tracing, outside temperatures in the range from
-50 to +50 °C can be simulated. During simulation, the actual, the composite and the
attenuated outside temperature will be overridden by the set simulated temperature.
During simulation, calculation of the 3 mentioned outside temperatures continues and
the temperatures are available again when simulation is completed.
The function is deactivated by setting -.- on this operating line, or automatically after a
timeout of 5 hours.
Line no.
Operating line
7170
Telephone customer service
Setting of phone number that appears on the info display.

6.11 Input / output test

Line no.
7700...7881
User Manual
6 The settings in detail
Output
K4
Q1
Q12
Q5
Q3
Q3
Q4
K6
Q2
Q6
Q20
Y1/Y2
closing
Y5/Y6
Q21
speed
Q22
Q23
Q15
Q18
K10
appears.
Operating line
State
On
On
On
Off
On
Off
On
On
On
Off
On
On
On
Off
CE1U2357en
2014-07-30

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents