Commissioning notes
Standards and certificates
Service notes
4/16
Building Technologies Division
When commissioning the plant, when carrying out maintenance work, or after longer off
periods, make the following safety checks:
Safety check to be carried out
a)
Burner startup with flame detector
darkened
b)
Burner startup with flame detector
exposed to extraneous light
c)
Simulation of flame failure during
operation. For that purpose, darken the
flame detector during operation and
maintain this state
Applied directives:
Low-voltage directive
Electromagnetic compatibility EMC
(immunity) *)
*) The compliance with EMC emission requirements must be checked after the burner control
is installed in equipment
Compliance with the regulations of the applied directives is verified by the
adherence to the following standards / regulations:
Household and similar electrical appliances - Safety
Electrical equipment of non-electric heated cooking and heating
appliances
The relevant valid edition of the standards can be found in the declaration
of conformity!
Note on DIN EN 60335-2-102
Household and similar electrical appliances - Safety - Part 2-102:
Particular requirements for gas, oil and solid-fuel burning appliances having electrical
connections. The electrical connections of the LOA and the AGK11 comply with the
requirements of EN 60335-2-102.
EAC Conformity mark (Eurasian Conformity mark)
ISO 9001:2008
ISO 14001:2004
OHSAS 18001:2007
China RoHS
Hazardous substances table:
http://www.siemens.com/download?A6V10883536
The service adapters can only be used for a short time. They may only be used in
supervised operation by qualified staff.
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170.
website:
https://www.add-furnace.com/
Line ID: @add11 Wechat ID: add0883001122
Lockout at the end of «TSA»
Lockout after approx. 40 seconds
Repetition followed by lockout at
the end of «TSA»
โทร: 02-888-3472
Anticipated response