6
Connect the input and ground wires to the terminal block according to Figure 19 and Table 1.
Figure 19. UPS Input Terminal Block
Table 1. UPS Wiring Specifications
Wire Function
Input
* Use a minimum:
S 10 AWG for equipment grounding wire, 75_C copper wire minimum
S 8 AWG for input line and neutral wires, 75_C copper wire minimum
7
Replace the terminal block cover.
8
Continue to the following section, "UPS Initial Startup."
Terminal Position
1
2
3
Terminal
UPS Wire Function
Position
1
Input Ground
2
L2/Neutral In
3
Terminal Wire
Size Rating*
5.26–16 mm
(10–6 AWG)
L1 In
Tightening Torque
2
2.49 Nm (22 lb in)
|
Installation
29