Page 2
Please read the information carefully, since it is provided for your personal safety and will also help prolong the service life of your SINAMICS G110 Inverter and the equipment you connect to it. WARNING This equipment contains dangerous voltages and controls potentially dangerous rotating mechanical parts.
Page 3
Before installing and commissioning, please read these safety instructions and warnings carefully and all the warning labels attached to the equipment. Make sure that the warning labels are kept in a legible condition and replace missing or damaged labels. SINAMICS G110 Operating Instructions (Compact) Operating Instructions (Compact)
Specific factory settings for the analog version ............9 Specific factory settings for the USS version............10 DIP switches ......................10 Communications....................11 Establishing communications SINAMICS G110 STARTER ......11 BOP (Option) ......................12 Buttons and their Functions ..................12 Changing parameters using as an example P0003 "Access level"......
Digital input 0 DIN1 Digital input 1 DIN2 Digital input 2 Isolated output +24 V / 50 mA Output 0 V Variant Analog Output +10 V RS485 P+ Analog input RS485 N- Output 0 V SINAMICS G110 Operating Instructions (Compact)
Issue 11/04 3 Factory setting Factory setting The SINAMICS G110 frequency inverter has already been programmed at the factory (motor parameters P0304, P0305, P0307, P0310), for standard V/f applications on Siemens 4-pole asynchronous motors 1LA that have the same power rating as the inverters...
Example, USS bus DIP switches The default motor base frequency of the SINAMICS G110 inverter is 50 Hz. For motors, which are designed for a base frequency of 60 Hz, the inverters can be set to this frequency via a DIP switch.
STARTER and SINAMICS G110: PC <-> frequency inverter connecting kit (order no 6SL3255-0AA00-2AA0) BOP, as far as the USS standard settings already kept in the Sinamics G110 shall be changed (order no 6SL3255-0AA00-4BA0) PC <-> SINAMICS G110 connecting Kit SINAMICS G110 USS settings, refer to Section 6.2.1, Page 17.
If alarm and fault messages are present, then these can be acknowledged by pressing key Fn. Access Pressing this button allows access to the parameters. parameters Increase Pressing this button increases the displayed value. value Decrease Pressing this button decreases the displayed value. value SINAMICS G110 Operating Instructions (Compact)
4 Press to the required value (example: 3) 5 Press to confirm and store the value 6 Now access level 3 is set and all level 1 to level 3 parameters are visible to the user. SINAMICS G110 Operating Instructions (Compact)
11. The BOP can now be removed from the inverter. Download (BOP SINAMICS G110) 1. Connect the BOP to the SINAMICS G110 inverter, in which the parameter set is to be downloaded. 2. Ensure power is applied to the inverter.
The quick commissioning function will adapt the inverter to the motor and will set important technological parameters. The quick commissioning can be omitted if a 4-pole 1LA Siemens motor will be used, which matches the rating data of the frequency inverter.
Page 16
Time taken for motor to decelerate from maximum motor frequency (P1082) down to standstill when no rounding is used 5.00 s OFF3 ramp-down time P1135 =... (enters the fast stop ramp-down time in s) Defines ramp-down time from maximum frequency to standstill for OFF3 command. SINAMICS G110 Operating Instructions (Compact)
19200 baud Defines the number of 16-bit words in PZD part of USS telegram. 38400 baud 57600 baud USS PKW length P2013 =... Defines the number of 16-bit words in PKW part of USS telegram. SINAMICS G110 Operating Instructions (Compact)
12.3 ms debounce time 2-wire/3wire control method P0727 =... Determines the control method using the terminals 0 Siemens Standard (Start / Direction) 1 2-wire (FWD / REV) 2 3-wire (FWD P / REV P) 3 3-wire (Start P / Direction) "P"...
2 / 5 Selection of frequency setpoint P1000 G110 AIN G110 USS Settings P1000 =... No main setpoint – MOP setpoint see 6.2.7 Analog setpoint – see 6.2.6 Fixed frequency see 6.2.8 – see 6.2.1 SINAMICS G110 Operating Instructions (Compact)
P0719 = 0, P0700 = 5, P1000 = 1 USS control word USS control word USS * P0719 = 1, P0700 = 5 r2036 Bit13 r2036 Bit14 P0719 = 51 *) SINAMICS G110 CPM110 USS only SINAMICS G110 Operating Instructions (Compact)