Siemens SINAMICS G110 Operating Instructions Manual
Hide thumbs Also See for SINAMICS G110:

Advertisement

Operating Instructions (Compact)
Issue 11/04
sinamics
SINAMICS G110

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SINAMICS G110

  • Page 1 Operating Instructions (Compact) Issue 11/04 sinamics SINAMICS G110...
  • Page 2 Please read the information carefully, since it is provided for your personal safety and will also help prolong the service life of your SINAMICS G110 Inverter and the equipment you connect to it. WARNING This equipment contains dangerous voltages and controls potentially dangerous rotating mechanical parts.
  • Page 3 Before installing and commissioning, please read these safety instructions and warnings carefully and all the warning labels attached to the equipment. Make sure that the warning labels are kept in a legible condition and replace missing or damaged labels. SINAMICS G110 Operating Instructions (Compact) Operating Instructions (Compact)
  • Page 4 Warnings, Cautions and Notes Issue 11/04 SINAMICS G110 Operating Instructions (Compact)
  • Page 5: Table Of Contents

    Specific factory settings for the analog version ............9 Specific factory settings for the USS version............10 DIP switches ......................10 Communications....................11 Establishing communications SINAMICS G110 STARTER ......11 BOP (Option) ......................12 Buttons and their Functions ..................12 Changing parameters using as an example P0003 "Access level"......
  • Page 6: Installation

    Drilling Dimensions Tightening Torque Size Bolts Nm (lbf.in) mm (Inch) mm (Inch) 140 (5.51) 79 (3.11) 2xM4 2,5 (22.12) 135 (5.31) 127 (5.00) 4xM4 140 (5.51) 170 (6.70) 4xM5 4,0 (35.40) Fig. 1-2 Mounting dimensions SINAMICS G110 Operating Instructions (Compact)
  • Page 7: Electrical Installation

    Digital input 0 DIN1 Digital input 1 DIN2 Digital input 2 Isolated output +24 V / 50 mA Output 0 V Variant Analog Output +10 V RS485 P+ Analog input RS485 N- Output 0 V SINAMICS G110 Operating Instructions (Compact)
  • Page 8: Block Diagram

    2 Electrical Installation Issue 11/04 Block diagram Fig. 2-2 Inverter block diagram SINAMICS G110 Operating Instructions (Compact)
  • Page 9: Factory Setting

    Issue 11/04 3 Factory setting Factory setting The SINAMICS G110 frequency inverter has already been programmed at the factory (motor parameters P0304, P0305, P0307, P0310), for standard V/f applications on Siemens 4-pole asynchronous motors 1LA that have the same power rating as the inverters...
  • Page 10: Specific Factory Settings For The Uss Version

    Example, USS bus DIP switches The default motor base frequency of the SINAMICS G110 inverter is 50 Hz. For motors, which are designed for a base frequency of 60 Hz, the inverters can be set to this frequency via a DIP switch.
  • Page 11: Communications

    STARTER and SINAMICS G110: PC <-> frequency inverter connecting kit (order no 6SL3255-0AA00-2AA0) BOP, as far as the USS standard settings already kept in the Sinamics G110 shall be changed (order no 6SL3255-0AA00-4BA0) PC <-> SINAMICS G110 connecting Kit SINAMICS G110 USS settings, refer to Section 6.2.1, Page 17.
  • Page 12: Bop (Option)

    If alarm and fault messages are present, then these can be acknowledged by pressing key Fn. Access Pressing this button allows access to the parameters. parameters Increase Pressing this button increases the displayed value. value Decrease Pressing this button decreases the displayed value. value SINAMICS G110 Operating Instructions (Compact)
  • Page 13: Changing Parameters Using As An Example P0003 "Access Level

    4 Press to the required value (example: 3) 5 Press to confirm and store the value 6 Now access level 3 is set and all level 1 to level 3 parameters are visible to the user. SINAMICS G110 Operating Instructions (Compact)
  • Page 14: Cloning Parameters With The Bop

    11. The BOP can now be removed from the inverter. Download (BOP SINAMICS G110) 1. Connect the BOP to the SINAMICS G110 inverter, in which the parameter set is to be downloaded. 2. Ensure power is applied to the inverter.
  • Page 15: Commissioning

    The quick commissioning function will adapt the inverter to the motor and will set important technological parameters. The quick commissioning can be omitted if a 4-pole 1LA Siemens motor will be used, which matches the rating data of the frequency inverter.
  • Page 16 Time taken for motor to decelerate from maximum motor frequency (P1082) down to standstill when no rounding is used 5.00 s OFF3 ramp-down time P1135 =... (enters the fast stop ramp-down time in s) Defines ramp-down time from maximum frequency to standstill for OFF3 command. SINAMICS G110 Operating Instructions (Compact)
  • Page 17: Commissioning The Application

    19200 baud Defines the number of 16-bit words in PZD part of USS telegram. 38400 baud 57600 baud USS PKW length P2013 =... Defines the number of 16-bit words in PKW part of USS telegram. SINAMICS G110 Operating Instructions (Compact)
  • Page 18: Selection Of Command Source

    12.3 ms debounce time 2-wire/3wire control method P0727 =... Determines the control method using the terminals 0 Siemens Standard (Start / Direction) 1 2-wire (FWD / REV) 2 3-wire (FWD P / REV P) 3 3-wire (Start P / Direction) "P"...
  • Page 19: Digital Output (Dout)

    2 / 5 Selection of frequency setpoint P1000 G110 AIN G110 USS Settings P1000 =... No main setpoint – MOP setpoint see 6.2.7 Analog setpoint – see 6.2.6 Fixed frequency see 6.2.8 – see 6.2.1 SINAMICS G110 Operating Instructions (Compact)
  • Page 20: Analog Input (Adc)

    P0719 = 0, P0700 = 5, P1000 = 1 USS control word USS control word USS * P0719 = 1, P0700 = 5 r2036 Bit13 r2036 Bit14 P0719 = 51 *) SINAMICS G110 CPM110 USS only SINAMICS G110 Operating Instructions (Compact)