3.10

Routing

Routing describes the cross-network transfer of information from Network x to Network y.
3.10.1

Routing on SIMOTION D

Routing between the different interfaces
The Ethernet interfaces of the D4x5-2
● X127 P1 and X130 P1 (for D4x5-2 DP/PN) or
● X127 P1, X120 P1 and X130 P1 (for D4x5-2 DP)
each form a separate IP subnet.
The D4x5-2 DP/PN onboard PROFINET IO interface (X150, P1-P3) and the optional second
PROFINET IO interface with CBE30-2 (X1400, P1-P4) also each form a separate IP subnet.
All ports of a PROFINET IO interface always belong to the same IP subnet.
● IP routing from IP subnet to IP subnet is not supported. You can use an external IP router
● The S7 routing between PROFINET/Ethernet subnets and also to PROFIBUS is possible.
There are therefore the following options for connecting a PG/PC or HMI device to a
SIMOTION D using S7 routing.
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 02/2012
for this
Connecting
3.10 Routing
77