Page 1
D7030X-S8 Installation Guide Eight-Zone LED Annunciator...
Page 2
Notices Notices This guide coves the installation of the D7030X-S8 Eight-Zone LED Annunicator in a fire system supervised by a D7024 Fire Alarm Control Panel (FACP). Install, test, and maintain the D7030X-S8 according to these instructions, NFPA 72, local codes, and the Authority Having Jurisdiction (AHJ).
Bus A or Option Bus B) through the three-gang box knockout and to the annunciator terminal strip (Figure 4). The D7030X-S8 must have a unique address set within its address pins. This address cannot conflict with other Figure 4: D7030X-S8 Terminal Wiring annunciator addresses or other option bus device addresses.
Page 4
D7030X-S8 | Installation Guide | 5.0 Adding External LEDs 4. Follow the wiring guidelines: Adding External LEDs • Do not use shielded cable. Add external LEDs for remote indication of the • Do not exceed 1000 ft (305 m) between the individual zones by connecting to the remote LED pins FACP and the annunciator.
Page 5
11. Press [2] for Output Zone and enter the output zone 3. Position the faceplate. for this point. 4. Secure the D7030X-S8 to the box using the screws 12. Repeat Steps 6 and 7 until all points are (supplied). programmed.
D7030X-S8, an additional 8 LED zones appear allowing the D7030X-S8 and D7032 combination to show a total of 16 LED zones. If no D7032 is attached, only the lower 8 zones appear. Up to 8 D7030X-S8 and D7032 combinations can connect to the D7024 FACP.