1.4.2 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed on only to authorized persons or companies with the required technical knowledge. 7 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL..
Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
For use in connection with Siemens 2-port or 3-port valves with 20/40 mm stroke, SAX.., SAV.. as control or shutoff valves for HVAC plants. SAY.. For the operation of Siemens combi valves of type VPI46.40F9.5Q and VPI46.50F12Q with 15 mm stroke as control valves in ventilation, air conditioning, and district heating systems.
1 pc. M5 x 20 mm incl. 1 pc. 12 mm ASK32N 4 pcs. M6 x 16 mm 1 pc. 12mm 1 pc. M5 x 20 mm incl. 12 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Engineering 2020-01-30...
Page 13
2 pcs. M8 x 50 mm 1 pc. 12 mm 1 pc. M5 x 20 mm incl. 1 pc. 16 mm 16 mm 12 mm 13 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Engineering 2020-01-30...
Page 15
Valves no longer in the active sale SAV..: This product line of actuators might not be available in all countries. Please talk to your local contact or consult your local internet pages of www.buildingtechnologies.siemens.com. Only in compbination with SKC.. 15 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL..
Page 17
Valves no longer in the active sale SAV..: This product line of actuators might not be available in all countries. Please talk to your local contact or consult your local internet pages of www.buildingtechnologies.siemens.com Only in combination with SKC.. 17 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL..
VKF41.. maximum flow speed with SAL.T0 actuator with water DN150/200 = 2.5 m/s, with SAL.T40 actuator with water DN150/200 = 4 m/s VKF46.. maximum flow speed water = 4.5 m/s, air 40 m/s 18 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
The signal peaks that occur in the potentiometer ASZ7.5 may result in error messages on Siemens SIMATIC. This is not the case when combined with Siemens HVAC controllers. The reason is that SIMATIC has a higher resolution and faster response time.
SAX81.03U SQX31.06: Actuator for gas valves. Either replace complete valve-actuator combination or clarify required positioning time and replace only actuator. Consider if mounting set is required. 20 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
· Non-observance of the above may result in accidents and fires! · Do not touch the hot parts without prior protective measures to avoid burns. 21 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Engineering...
4 screws 2 pcs. M5 x 20 mm 2 pcs. M6 x 20 mm Single components from the spare part sets are not available. 22 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Engineering 2020-01-30...
· The operating voltage drop at AC/DC 24 V may be a maximum of 8% (4% above the G0 wire). Basic diagram − voltage drop across the power supply cables 23 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Engineering 2020-01-30...
The engineering data specified in chapter "Equipment combinations" (page 14) are only guaranteed in connection with the Siemens valves listed. Note When using the actuators in connection with valves of other manufacture, correct functioning must be ensured by the user, and Siemens will assume no responsibility. 24 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL..
Risk of burns from hot surfaces! If you touch heated parts, you will get burns as result. · Allow to cool parts. · Wear protective gloves. Actuator’s stem retracted 25 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
If so, please take care for correct mounting, either by turning the actuator or by adjusting the fitting (e.g. use a second sealing to change fitting position). 26 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
If you touch heated parts, you will get burns as result. · Allow to cool parts. · Wear protective gloves. 5 mm 5 mm 27 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Page 28
5 mm 4 mm Angle position errors between actuator shaft and valve stem must be corrected via manual control (refer to "Manual adjuster" page 69). 28 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling...
If you touch heated parts, you will get burns as result. · Allow to cool parts. · Wear protective gloves. 10 mm, ASK31N ASK32N 13 mm 90° 29 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Page 30
4 mm, 5 mm 4 mm, 5 mm counterclockwise ASK31N 12 mm ASK32N 3.2a 3.2b 4 mm, 5 mm 4 mm, 5 mm ASK31N 12 mm ASK32N 30 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Page 31
For further mounting positions of VBF 21.. and routing of the connection cables the rotary actuators and adapters must be mounted according to the sketches above. 31 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
If you touch heated parts, you will get burns as result. · Allow to cool parts. · Wear protective gloves. 12 mm (DN 40…125) 16 mm (DN 150 / 200) 33 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Page 34
4 mm 6 mm 34 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
There is an immediate risk of fatal injury in case of contact with live parts of SA..31... · Disconnect actuator from power. Actuator is mechanically connected to a Siemens valve. Observe compatibility and choice of combinations. Refer to "Accessories" (page 19).
Page 36
If a live wire gets in contact with the screws the whole actuator housing is a live. · Fit the screw covers first. Plug-in space A No.: 1 Turn to 0% 36 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Page 37
Connection terminals" (page 77) Function module First, observe "Special notes on mounting” (page 35). AZX61.1 Set function module (page 54) Nr.: 3 Plug-in space B 37 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Page 38
· Fit the screw covers first. Plug-in space A No.: 1 Adjust switch position (refer also to "Manual operation" page 69) 38 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Page 39
If a live wire gets in contact with the screws the whole actuator housing is a live. · Fit the screw covers first. Plug-in space B No.: 1 39 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Page 40
When fitting the stem heating element, stroke actuator and valve must be assembled. The stem heating element is powered separately. First, observe "Special notes on mounting” (page 35). 10 mm 14 mm 8 mm 40 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
US: ½“ installation EU: M20 Connection US: ½“ accessories Cable glands (not contained in scope of delivery) Metric Metric Inch thread ½“ 41 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Page 42
Prior to installation, the following preconditions must be satisfied: · Actuator is mechanically connected to a Siemens valve. · Housing cover is removed (step 6 "Special notes on mounting", page 35). Communicating Device contains fixed connecting actuators cable. Left cable duct used (A).
Before making the function check, the following preconditions must be satisfied: · Environmental conditions specified in chapter "Technical data" (page 73) · Actuator is mechanically connected to a Siemens valve · Actuator is in "Manual operation" mode (page 69). The actuator can be operated with the help of the "Manual adjuster" (see page 69).
Page 44
· If function module AZX61.1 is used, observe information given in chapter Notes "Changeover of acting direction" (page 55). · Observe information given in chapter "Acting direction and flow characteristic" on page 57. 44 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Page 45
(65%) position (65%) Actuator’s stem Actuator’s spindle Check position value with maintains the maintains the ~ 485 Ω ~ 511 Ω ohmmeter position position 45 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
· The actuator parameters (direction for opening, position limits, position adjustment etc.) can be read via the Modbus register. Documents can be downloaded at http://www.siemens.com/bt/download Full or partial configuration via bus The actuators can be configured via bus connection if the settings prior to commissioning allow for a connection to the Modbus master/programming tool (no address conflicts and correct baud rates/transmission format settings).
Page 47
1s On / 5s Off Internal error 0.1s On / 1s Off Invalid configuration, e.g. Min = Max Blue Flickering once after address indication Bus termination active 47 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Page 48
7. Save address: Press button until LED is – release button à The address is saved and displayed 1x for confirmation 48 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
· Dispose of the device through channels provided for this purpose. · Comply with all local and currently applicable laws and regulations. 49 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Handling 2020-01-30...
Observe information given in chapter "Acting direction and flow characteristic" on page 57. Internal control ensures very constant positioning times and determination of the actuator’s position. 50 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control...
Page 51
Calculated position Actual position time [ms] (power applied) applied Accurate position feedback is made possible with the help of a potentiometer (page 71). 51 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2020-01-30...
Notes "Changeover of acting direction" (page 55). · Observe the information given in chapter "Acting direction and flow characteristic" on page 57. 53 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2020-01-30...
· Can only be used with voltage input. Notes · Maximum input voltage is DC 30 V. If the configuration is invalid, the actuator operates on DC 0…10 V. 54 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control...
Y = 0 V resp. Z = 0 Ω. This applies to all Siemens valves according to "Equipment combinations" (page 14). · With valves whose stem is retracted in the fully closed position, "direct acting"...
Positioning signal Stroke Volumetric flow Acting direction: Direct Acting direction: Reverse Note SAX61.03/MO: Positioning signal and flow characteristic selection are not permissible 56 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2020-01-30...
The position feedback U (DC 0...10 V) is always proportional to stroke H of the actuator’s stem. Actuator Actuator Positioning signal Y, Z Position feedback U log = equal- percentage lin = linear 57 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2020-01-30...
With this function it’s granted that the position feedback U – which was zero during manual operation and synchronization - always represents the real mechanical position of the actuator. 58 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
(2), valve opens. Detection of lower end position. · The detected values are stored (3). Then the actuator follows the positioning signal. 59 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2020-01-30...
50%. From now on, the actuator follows the positioning signal. When the valve plug reaches its seat for the first time, the actuator readjusts its stroke model. 60 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control...
If the attempts made are unsuccessful, the actuator continues to follow the positioning signal within the restricted range only and the actuator LED continues to blink green (refer to "Indicators" on page 70). 61 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
(page 43). During commissioning, the actuator detects the valve’s end positions and files the exact stroke in its internal memory. 63 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
Notes The self test can only be performed if bit 4 = 0 in register 769 “Status”, meaning there is concurrently no clogging or manual operation. 66 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure...
Page 67
“Load” is called within 60 seconds in this “Bus config. register. Otherwise, all changes are discarded. Command” 67 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control...
The stem coupling (1) and neck coupling (2) Mounting sets are available for use with butterfly ensures full backward compatibility with all types and slipper valves. of Siemens large-stroke valves produced since 1975. 4.14.3 Manual adjuster Automatic When the motor drives the manual adjuster turns.
Start calibration again. Calibration error Blinking If error re-occurs immediately: check Clogged valve valve Dark Dark No power or electronics faulty Check operating voltage 70 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2020-01-30...
SAV.. R = 0 + 8.55 Ohm x rotary angle (°) SAL.. Actuator position in relation to nominal stroke/nominal angular rotation [%] 71 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control 2020-01-30...
Mounting sets ASK31N, ASK32N, ASK33N and ASK35Nenable the actuators to be ASK3..N fitted to slipper valves VBF21.., DN65…150 and butterfly valves VKF41.. and VKF45 (page 27-34). 72 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Functions and control...
Switch-on current 3-position actuators (typical) SA..31.. 2.3 A 2.3 A 2.3 A 2.3 A SA..81.. 4.5 A 4.5 A 4.5 A 4.5 A 73 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Technical data 2020-01-30...
Page 74
As per EN 60730 tion Actuators SA..31.. AC 230 V Actuators SA..61.. AC / DC 24 V Actuators SA..81.. AC / DC 24 V 74 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Technical data 2020-01-30...
Page 75
AWG = American wire gauge Also with weather shield ASK39.1 SA..61../MO are not suitable for outdoor applications. Up to 150 °C with horizontal mounting position The documents can be downloaded from http://siemens.com/bt/download. UL recognized component 75 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves...
1x ASC10.51 AC 24 V...230 V / 6 (2) A S3 S2 or 1 x ASZ7.5 S3 S2 AC/DC 24 V 76 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Connection diagrams and dimensions 2020-01-30...
AC/DC 24 V / 30 W / 50 VA / inrush current max. 8.5 A Stem heating element ASZ6.6 System neutral (SN) (red) System potential (SP) (black) 77 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Connection diagrams and dimensions 2020-01-30...
SAX..U: 1.850 kg SAY..U: 1.850 kg Device equipped with a fixed connection cable – Left cable entry is used Dimensions in mm 80 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Connection diagrams and dimensions...
6.4.2 External Modbus converter Type [mm] [kg] 0.15 SA../MO Already included in total weight Dimensions in mm 81 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Connection diagrams and dimensions 2020-01-30...
1.475 1.600 1.625 With ASK39.1 1.710 1.835 1.860 With mounting set ASK3..N Type SAL.. with ASK3..N With ASK39.1 Dimensions in mm 82 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Connection diagrams and dimensions 2020-01-30...
/ maxV Maximum permissible differential pressure at which the motorized valve will close Δp securely against the pressure (close off pressure). slotted screwdriver 84 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Glossary 2020-01-30...
Page 85
Stroke actuators ........80, 81 Disengaging the fixing ........69 Direct acting..........55, 57 Fixing the coupling .......... 69 Directives ............75 Manual operation ..........69 85 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Index 2020-01-3028...
Page 86
Rotary actuators SQL.. to SAL......21 Δp ............14, 16, 18 Stroke actuators SQX.. to SAX......20 Δp ..............16, 18 Frei verwendbar 86 / 87 Siemens Actuators SAX.., SAY.., SAV.., SAL.. for valves CE1P4040en Smart Infrastructure Index 2020-01-30...