HART function
7.2 HART system connection
up of data records that are transferred internally between the IM and I/O module via the ET
200SP HA IO device. The data records must be created and interpreted by the client.
• HART signal (Page 41)
• HART configuration tool (Page 40)
• HART device status (Page 41)
Configuration
You configure the individual channels with respect to the actual analog value output and the use
of the HART variables in the input address space of the module.
You can configure one field device per channel. The configuration/parameter assignment of the
connected field device is then carried out from this configured field device using PDM or the EDD
for the ET 200SP HA.
Parameter reassignment of the field devices
The I/O module generally accepts triggered reconfigurations for field devices. Access rights can
only be allocated in the parameter assignment tool.
To reassign parameters of the field devices connected to the I/O module, proceed as follows:
1. You start the parameter reassignment of a field device using a HART command that you enter
using the SIMATIC PDM parameter assignment tool.
2. After you complete re-parameterization of a HART field device, the corresponding bit is set in
the HART device status of the connected field device (in the 2nd status byte).
3. The re-parameterization of the field device causes the analog module to issue a maintenance
message "Configuration changed", if this is enabled. This maintenance message should be
regarded as a notice and not an error. It is automatically deleted again by the I/O module after
approximately 1 minute.
Maintenance events (Page 65)
If enabled, a maintenance message can also be triggered by a new parameter assignment with
the handheld device.
7.2.2

HART configuration tool

Definition
The HART parameters can be set either using an external hand-held device (HART Handheld) or
a HART configuration tool (PDM). Both assume the function of a "client":
The parameter assignment tool affects the entire I/O module; the HART handheld is connected
in parallel to the field device.
40
AI 4xI 2-/4-wire HART ISOL HA
Equipment Manual, 07/2022, A5E50101523-AB