Permitting Changes To The Device Name And Ip Address Directly On The Device - Siemens SIMATIC ET 200AL Compact Operating Instructions

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Parameter assignment/addressing
4.2 Device name and IP address
4.2.5
Permitting changes to the device name and IP address directly on the
device
Introduction
Machines are frequently commissioned on site or integrated into the existing infrastructure
without STEP 7. You can find typical applications in all areas of the series machine building.
Alternative means for assigning the IP address are available for this.
Procedure
1. In the network or device view of the STEP 7 Hardware and Network editor, select the
PROFINET interface of an IO controller.
2. Navigate in the Inspector window to "Ethernet addresses".
3. Select the "IP address is set directly at the device" option in the "IP protocol" area.
4. In the "PROFINET" area, select the " PROFINET device name is set directly at the device"
check box.
Figure 3-305  Setting the device name and IP address on the device
NOTE
Gateway
When you operate a PROFINET device with the option "Allow adaption of the device
name/IP address directly on device", you cannot use this PROFINET device as gateway for
S7 routing.
1706
PROFINET with STEP 7
Function Manual, 11/2023, A5E03444486-AN