DX4020-EXP | Installation Guide | 2. Overview
2.
Overview
2.1
Specifications
Table 1: DX4020 Specifications
Dimensions
7.6 cm x 12.7 cm (3 in. x 5 in.)
Current Draw
84 mA max, 80 mA nominal 10 Base-T
110 mA max, 100 mA nominal 100 Base-T
Operation
12 VDC Nominal
Voltage
Connectors
Control
Panel
LAN/WAN
Ethernet
Category 3 or better unshielded twisted
Cable
pair
Max Length
Interface
IEEE 802.3
Compatibility
Control Panel
D9412G, D7412G,
D7212G, D9412, D9112,
D7412, D7212
DS7240V2, DS7220V2
DS7400xi
Default IP
0.0.0.0 (DHCP mode)
Address
Bosch Security Sys | 8/04 | F01U002192B
Option/Data Bus Terminal
Strip
RJ-45 Modular Jack
(Ethernet)
100 m (328 ft)
Firmware
6.3 or later
2.xx or later
4.10 or later
2.2
System Overview
See Figure 2 for a general system connection of the
following devices: a compatible Bosch Security Systems
control panel, a DX4020 Network Interface Module, a
D6600 Receiver, and a D6680 Network Adapter.
Figure 2: System Connections Overview
7
1
3
10
7
6
1 - Compatible Bosch Control Panel
2 - DX4020 Network Interface Module – Ethernet
3 - Host PC running D6200 Programming
Administrative Software
4 - Ethernet network
5 - D6680 Network Adapter
6 - D6600 Central Station Receiver
7 - Connection – Compatible Bosch Control Panel
Data Bus to DX4020 Data Bus terminals
8 - Connection – Ethernet network to Host PC
Ethernet Network Interface Card (NIC
9 - Connection – Ethernet network to D6680
10 - Connection – D6680 to D6600 COM4 Port
EN | 3
2
9
8
4
9
5