Auxiliary Voltage - Siemens siprotec SJ62 User Manual

Multi-functional protective relay with local control
Table of Contents

Advertisement

4 Technical Data
4.1.2

Auxiliary Voltage

DC Voltage
AC Voltage
445
Voltage Supply via Integrated Converter
Rated auxiliary DC V
Aux
Permissible Voltage Ranges
Rated auxiliary DC V
Aux
Permissible Voltage Ranges
AC Ripple Voltage,
Peak to Peak, IEC 60255-11
Power Input
7SJ621,
7SJ622
7SJ631
7SJ632,
7SJ633
7SJ635,
7SJ636
7SJ640
7SJ641
7SJ642
7SJ645
Bridging Time for Failure/Short-Circuit,
IEC 60255–11
(in not energized operation)
Voltage Supply via Integrated Converter
Nominal Auxiliary Voltage AC V
Permissible Voltage Ranges
Power input (at 115 VAC / 230 VAC)
7SJ621,
7SJ622
7SJ631
7SJ632,
7SJ633
7SJ635,
7SJ636
7SJ640
7SJ641
7SJ642
7SJ645
Bridging Time for Failure/Short-Circuit (in not
energized operation)
24/48 VDC
19 to 58 VDC
110/125/220/250 VDC
88 to 300 VDC
15 % of the auxiliary voltage
Quiescent
Approx. 4 W
Approx. 4 W
Approx. 5.5 W
Approx. 7 W
Approx. 5 W
Approx. 5.5 W
Approx. 5.5 W
Approx. 6.5 W
≥ 50 ms at V ≥ 110 V–
≥ 20 ms at V ≥ 24 V–
115 VAC
Aux
92 to 132 VAC
Quiescent
Approx. 3 VA
Approx. 3 VA
Approx. 5 VA
Approx. 7 VA
Approx. 7 VA
Approx. 9 VA
Approx. 9 VA
Approx. 12 VA
200 ms
60/110/125 VDC
48 to 150 VDC
Energized
Approx. 7 W
Approx. 10 W
Approx. 16 W
Approx. 20 W
Approx. 9 W
Approx. 13 W
Approx. 12 W
Approx. 15 W
230 VAC
184 to 265 VAC
Energized
Approx. 9 VA
Approx. 12 VA
Approx. 18 VA
Approx. 23 VA
Approx. 12 VA
Approx. 19.5 VA
Approx. 18.5 VA
Approx. 23 VA
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015