2.25 Function Control and Circuit Breaker Test
Table 2-20
Serial
No.
1
1-pole TRIP/CLOSE-cycle phase L1
2
1-pole TRIP/CLOSE-cycle phase L2
3
1-pole TRIP/CLOSE-cycle phase L3
4
3-pole TRIP/CLOSE-cycle
Associated close command
Figure 2-228

2.25.2.2 Information List

No.
Information
-
CB1tst L1
-
CB1tst L2
-
CB1tst L3
-
CB1tst 123
7325
CB1-TESTtrip L1
7326
CB1-TESTtrip L2
7327
CB1-TESTtrip L3
7328
CB1-TESTtrip123
7329
CB1-TEST close
7345
CB-TEST running
7346
CB-TSTstop FLT.
7347
CB-TSTstop OPEN
7348
CB-TSTstop NOTr
7349
CB-TSTstop CLOS
7350
CB-TST .OK.
458
Circuit breaker test programs
Test Programs
TRIP-CLOSE test cycle
Type of In-
formation
-
-
-
-
OUT
OUT
OUT
OUT
OUT
OUT
OUT_Ev
OUT_Ev
OUT_Ev
OUT_Ev
OUT_Ev
Circuit
Output Indications (No.)
Breaker
CB1-TESTtrip L1 (7325)
CB1-TESTtrip L2 (7326)
CB 1
CB1-TESTtrip L3 (7327)
CB1-TESTtrip 123 (7328)
CB1-TEST CLOSE (7329)
Comments
CB1-TEST trip/close - Only L1
CB1-TEST trip/close - Only L2
CB1-TEST trip/close - Only L3
CB1-TEST trip/close Phases L123
CB1-TEST TRIP command - Only L1
CB1-TEST TRIP command - Only L2
CB1-TEST TRIP command - Only L3
CB1-TEST TRIP command L123
CB1-TEST CLOSE command
CB-TEST is in progress
CB-TEST canceled due to Power Sys. Fault
CB-TEST canceled due to CB already OPEN
CB-TEST canceled due to CB was NOT READY
CB-TEST canceled due to CB stayed CLOSED
CB-TEST was successful
C53000-G1176-C169-5, Release date 02.2011
SIPROTEC, 7SD5, Manual