2.26.11 Energy
Metered values for active and reactive power are determined in the background by the processor system. They
can be called up at the front of the device, read out via the operating interface using a PC with DIGSI, or trans-
ferred to a central master station via the system interface.
2.26.11.1Energy Metering
7SD5 integrates the calculated power which is then made available with the measured values. The compo-
nents as listed in table 2-24 can be read out. The signs of the operating values depend on the setting at address
1107 P,Q sign (see Section 2.26.4 under margin heading „Display of Measured Values").
It is important to remember that 7SD5 is, above all, a protection device. The accuracy of the metered values
depends on the instrument transformers (normally protection core) and the device tolerances. The metering is
therefore not suited for tariff purposes.
The counters can be reset to zero or any initial value (see also SIPROTEC 4 System Description).
Table 2-24
2.26.11.2Setting Notes
Retrieving parameters
The SIPROTEC System Description describes in detail how to read out the statistical counters via the device
front panel or DIGSI. The values are added up in direction of the protected object, provided the direction was
set as „forward" (address 201).
2.26.11.3Information List
No.
Information
-
Meter res
888
Wp(puls)
889
Wq(puls)
916
WpΔ=
917
WqΔ=
924
Wp+=
925
Wq+=
928
Wp-=
929
Wq-=
SIPROTEC, 7SD5, Manual
C53000-G1176-C169-5, Release date 02.2011
Operational metered values
Measured values
W
+
Active power, output
p
W
–
Active power, input
p
W
+
Reactive power, output
q
W
–
Reactive power, input
q
Type of In-
formation
IntSP_Ev
PMV
PMV
-
-
MVMV
MVMV
MVMV
MVMV
kWh, MWh, GWh
kWh, MWh, GWh
kVARh, MVARh, GVARh
kVARh, MVARh, GVARh
Comments
Reset meter
Pulsed Energy Wp (active)
Pulsed Energy Wq (reactive)
Increment of active energy
Increment of reactive energy
Wp Forward
Wq Forward
Wp Reverse
Wq Reverse
Functions
2.26 Additional Functions
Primary
485