vacon • 66
Table 20. Technical specifications for size FI9-FI14 inverter units (INU)
Ambient
conditions
EMC (at default
settings)
Safety
Control
connections
5
Ambient operating
temperature
Storage temperature
Relative humidity
Air quality:
- chemical vapours
- mechanical particles
Altitude
Vibration
EN50178, EN60068-2-6
Shock
EN50178, EN60068-2-27
Heat loss
Cooling air required
Enclosure class
Immunity
Analogue input voltage
Analogue input current
Digital inputs (6)
Auxiliary voltage
Output reference voltage +10 V, +3%, max. load 10 mA
Analogue output
Digital outputs
Relay outputs
–10°C (no frost)...+40°C
–40°C...+70°C
0 to 95% RH, non-condensing, non-corrosive,
no dripping water
IEC 721-3-3, unit in operation, Class 3C2
IEC 721-3-3, unit in operation, Class 3S2
100% load capacity (no derating) up to 1000 m,
1% derating for each 100m above 1000 m;
max. 2000 m
Vibration amplitude 0.25 mm (peak) at 5-31 Hz
Max acceleration 1 G at 31-150 Hz
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max. 15 G, 11 ms (in package)
P
[kW] ≈ P
[kW] × 0.02
loss
mot
3
FI9: 1150 m
/h
3
FI10: 1400 m
/h
3
FI12: 2800 m
/h
3
FI13: 4200 m
/h
3
FI14: 2×4200 m
/h
IP00
Fulfil all EMC immunity requirements,
Level T
CE, UL, CUL
EN 61800-5-1 (2003)
(see unit nameplate for more detailed approvals)
0...+10 V, R
= 200 kΩ, (–10 V...+10 V joystick control)
i
Resolution 0.1%, accuracy ±1%
0(4)...20 mA, R
= 250 Ω differential
i
Positive or negative logic; 18-30 V
+24 V, ±15%, max. 250 mA
0(4)...20 mA; R
max. 500 Ω; Resolution 10 bit;
L
Accuracy ±2%
Open collector output, 50 mA / 48 V
2 programmable change over relay outputs
Switching capacity: 24 V
125 V
/ 0.4 A.
DC
Min. switching load: 5 V / 10 mA.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Technical information
DC
/ 8 A, 250 V
/ 8 A,
DC
AC