VACON · 18
Table 2: Quick Setup parameter group
Index
Parameter
P1.12
Preset frequency 2
P1.13
Acceleration Time 1
P1.14
Deceleration Time 1
Remote Control
P1.15
Place
P1.16
Automatic Reset
P1.17
Thermistor Fault
P1.18
PID Mini-Wizard *
P1.19
Multi-pump Wizard *
1
Min
Max
Unit
P3.3.1
300.00
Hz
0.1
3000.0
s
0.1
3000.0
s
1
2
0
1
0
3
0
1
0
1
QUICK STARTUP GUIDE
Default
ID
Description
Select with the digital
input: Preset frequency
15.00
106
selection 1 (P3.5.1.16)
(Default = Digital Input
5)
Gives the quantity of
time that is necessary
for the output fre-
20.0
103
quency to increase
from zero frequency to
the maximum fre-
quency.
Gives the quantity of
time that is necessary
for the output fre-
20.0
104
quency to decrease
from the maximum
frequency to zero fre-
quency.
The selection of the
remote control place
(start/stop).
1
172
0 = I/O control
1 = Fieldbus control
0
731
0 = Disabled
1 = Enabled
0 = No action
1 = Alarm
2 = Fault (Stop accord-
0
732
ing to stop mode)
3 = Fault (Stop by
coasting)
0 = Inactive
0
1803
1 = Activate
See
0 = Inactive
1 = Activate
0
See Chapter 2.2 Multi-
pump mini-wizard.
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205