Safety, approvals, EMC

7.2 Test voltage

7.2
Test voltage
Figure 7-1
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
● Connect the input terminals with one another
● Connect the output terminals with one another
Test (C)
● Connect the output terminals with one another and measure against PE
Table 7- 1
Test voltages for 6EP1333-3BA10 and 6EP1334-3BA10
Type test
Production test
Field test
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: <100 mA
52
Test voltage diagram
Test time
60 s
60 s
1 s
1 s
1 s
1 s
Prim ↔ sec (A)
4200 VDC
3000 VAC
4200 VDC
3000 VAC
2200 VDC
1500 VAC
Operating Instructions, 06.2014, C98130-A7548-A1-3-7629
Prim ↔ PE (B)
Sec ↔ PE (C)
2200 VDC
700 VDC
1500 VAC
500 VAC
4200 VDC
500 VDC
3000 VAC
350 VAC
2200 VDC
500 VDC
1500 VAC
350 VAC