Single duct
with el. heater
Digital input "Enable
electrical heater"
Control sequence
16 / 32
Siemens
Building Technologies
4.6.2
Single duct with electrical heater
If the selected application is "single duct & el. heater", then the controller works in
heating and cooling mode.
The output can be limited to a minimum and maximum value if required.
See section 4.5 "additional features".
In single duct applications with electrical heater, the controller controls an actuator
(valve, damper, VAV system, etc.) plus an auxiliary electrical heater.
Note: The setpoint for the electrical heater is limited by parameter "Maximum
heating setpoint" (P10).
Remote enabling/disabling of the electrical heater is possible via digital input X1/X2
for tariff regulations, energy saving etc.
Input X1 or X2 must be commissioned accordingly. See section "4.9 Multifunctional
input".
The diagram below shows the control sequence for continuous PI control.
Cooling and heating with electric heater
TR[°C] Room temperature
W
Room temperature setpoint
Y10
Control command "actuator"
Y21
Control command "electrical heater"
Note: The diagrams show the PI controller's proportional part only.
RDU340... Basic Documentation
Functions
Vmin
Min. limitation for output
Vmax Max. limitation for output
XpC
Proportional band "Cooling"
Xdz
Dead zone
SDH
Switching differential
CE1P3078en
2014-11-03