Device parameter
Response to current
limit violation
Lower current limit
Upper current limit
Blocking current
Blocking time
Response to
asymmetry
Asymmetry limit
Input signal extension
Input signal delay
Input 1 level
Input 2 level
Input 3 level
Input 4 level
Input 1 action
Input 2 action
Input 3 action
Input 4 action
M200D PROFIBUS/PROFINET
Manual, 08/2014, A5E01577426A/RS-AA/004
Default setting
System monitoring (Page 48)
Warning
18,75 %
112,5 %
800 %
1 s
Trip
30 %
0 ms
10 ms
Normally open
No action
Configuration / parameterization
Setting range
Warning
•
Trip
•
18.75 to 100% of I
•
e
0% (= deactivated)
•
Increment: 3,125 %
50 to 400% of I
•
e
0% (= deactivated)
•
Increment: 3,125 %
150 to 1000% von Ie
•
150 ... 800% of Ie
•
(sDS..., sRS...)
Increment: 50 %
1 to 5 s
Increment: 0.5 s
Warning
•
Trip
•
30 ... 60% (0 = deactivated)
Increment: 10 %
0 to 200 ms
Increment: 10 ms
10 ... 80 ms
Increment: 10 ms
Normally closed
•
Normally open
•
No action
•
Trip without restart
•
Trip with restart
•
Trip end position CW
•
Trip end position CCW
•
(RSte/sRSSte only)
Group warning
•
Manual operation local
•
Emergency start
•
Motor CW
•
Motor CCW (RSte/sRSSte only)
•
Quick stop
•
Trip reset
•
Cold run
•
5.2 Parameterize
129