Table of Contents 1 General..................3 Cer ficate for SIL 3 capability…………………………………...………….11 Introduc on................3 Typical wiring drawing……………………………………………...………….12 Product descrip on..............3 Installa on drawings for intrinsic safe and typical wiring……..13 General safety informa on.............3 Informa on on WEEE Direc ve 2002/96/EC (Waste Electrical and Electronic Equipment)......3 Pressure Equipment Direc ve (PED) (97/23/CE).....3 Use of instruc on..............3 2 Installa on in Hazardous Loca ons..........3...
/ or other ered within these operating instructions, please contact the manu- system components. facturer. ABB declares the contents of this manual are not part of any prior or existing agreements, commitments or legal relation- IMPORTANT (NOTE) This symbol indicates opera- ships and are not intended to amend those that are already in place.
In instances where corrosive and / or abrasive materials are be- ing measured, the user must check the level of resistance of all parts that are coming into contact with these materials. ABB offers guidance in the selection of material but does not accept liability in performing this service.
2.11 Protective grounding 2.8 IP Protection and designation All transmitters are supplied with an external ground connection for The housing for the MT-series transmitters is certified as con- protective grounding. Wire this ground connection to a suitable earth forming to protection type IP67 (according to IEC 60529) or Type ground.
ABB part number 010-1000-2, shall be according to the installation conditions. fitted to the input terminals. Refer to ABB Instruction docu- Flamepath joints are not intended to be repaired.
3.3 FM / US HazLoc ratings 3.4 CSA / Canadian HazLoc ratings Factory Mutual Research Corporation Canadian Standards Association MT50xx, MT51xx and MT52xx f/b abcdefghiFMjk : Model MT5000/5100/5200 Radar Level Transmitter XP-IS / I / 1 / ABCD / T6 Ta = 77°C; "[Ex ia] Associated Equipment"...
Service Department ware should be configured to detect fail-low (e.g. ≤4 mA) and fail at ABB via e-mail at service@ca.abb.com. The Service Depart- -high (e.g. ≥20 mA) inputs as an alarm value and possibly as re- ment will answer questions, provide additional assistance, and quiring a trip, in addition to the explicit use of 3.61 mA or 21 mA...
An MT5000 transmitter can be divided into three major compo- Note: A HART handheld device will communicate with the MT trans- mitter. The Device Descriptors are available on the ABB website. If nents, the sensor, the transmitter, and the output. All of these...
4.7.3.3 4–20mA Loop Check 4.10 Retirement Date for MT5X00 as a Functional Safety Device Without HART MT5X00 instruments shall not be used in a Safety Instrumented LOOP TEST is a function designed to simulate transmitter out- Function (SIF) after December 31 , 2022.
The user is responsible of verifying that current failure rates shown on the certificate meet the Safety Instrumented Function (SIF). The latest version of this certificate can be found on the web site at https://library.abb.com/ and searching for certificate Exida (SIL) ABB 16-12-C118 C001 MT5000 Series...
8 Installation Drawings for Intrinsic Safety & Standard Wiring Reference ABB drawing ELE9021 MT5000 Series, Intrinsically Safe Electrical Interconnection Diagram.
Page 14
8 Installation Drawings for Intrinsic Safety & Standard Wiring Reference ABB drawing ELE1034 MT5000 Series, FM & CSA Intrinsically Safe Electrical Interconnection Diagram.
Page 15
Québec, QC G1P 0B2, CANADA without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB Phone: +1 418 877 2944 does not accept any responsibility whatsoever Service: +1 225 408 0898 for potential errors or possible lack of information in this document.