Thermal Cutoff Switch - Hitachi APCQ Installation, Operation And Maintenance Instructions

Capacitor banks
Table of Contents

Advertisement

Important note: auxiliary power supply is included by default in the APCQ capacitor bank, there is no need to provide
an external power supply.

4.6. Thermal cutoff switch

Each APCQ capacitor bank cubicle includes a temperature-sensitive switch that trips the controller power supply
(hence RVC/RVT controller will be off) in case of over temperature above 60°C (or 140°F) inside the enclosure. In
such event, all the capacitors are switched off while fans keep running. Thermal cutoff switch automatically closes
when temperature goes down to normal conditions.
DANGER: When the thermal protection switches on, RVC/RVT controller is off but the capacitor bank is still
connected to the power supplies. See safety instructions and wait 5 minutes before the opening.
STATUS
Approved
Figure 11: Thermal cutoff switch
Figure 12: Location of thermal cutoff switch in APCQ-L
SECURITY LEVEL
Public
DOCUMENT ID
9AKK107680A4136
AP CQ CAPA CITO R BA NKS
REV.
LANG.
PAGE
E
en
14/47
© 2022 Hitachi Energy. All rights reserved.