The parameter is only relevant when the "HART enabled" parameter is activated.
5.4.5

Diagnostics: missing power supply voltage L+

Definition
Enabling of the diagnostics for missing or insufficient supply voltage L+.
This parameter is "activated" by default, cannot be changed and is for display purposes only.
5.4.6

Double-width terminal block

Definition
Specifies that a double-width terminal block is used in this slot.
This parameter is only active if the module is plugged into an even-numbered slot.
If set to "Yes", it is not possible to configure an additional module on the slot to the right of the
current slot.
When using the terminal blocks with potential distributors, you have to activate the parameter
"Double-width terminal block".
This parameter only affects the configuration in HW Config.
5.4.7

Smoothing

Definition
Compensates for measured value fluctuations.
The individual measured values are smoothed by filtering.
Description
The measured values are smoothed by a digital filter. Smoothing is achieved by the F-I/O module
calculating the moving average from a number of digitalized analog values specified with the
"Smoothing" parameter.
Smoothing can be set in 4 levels (1, 4, 16, 64 conversion cycles). The level determines the
number of analog signals to be used for generating the moving average.
When "1" is set, smoothing is deactivated.
F-AI 8xI 2-/4-wire HART HA
Equipment Manual, 09/2021, A5E50557845-AA
5.4 Explanation of the module/channel parameters
Parameters/address space
29