INSTRUCTION MANUAL
D1xB2X05, D1xB2X10, D1xB2X15 & D1xB2X21
Xenon Beacons
For use in Hazardous Locations
1) Warnings
 DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
 DO NOT OPEN WHEN ENERGISED
 POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
 HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
 DO NOT PAINT
 TO REDUCE THE RISK OF IGNITION OF
HAZARDOUS ATMOSPHERES, THE FIRST
CONDUIT RUN MUST HAVE A SEALING
FITTING CONNECTED WITHIN 18 INCHES
OF ENCLOSE. SUBSEQUENT CONDUIT
RUNS MUST HAVE A SEALING FITTING
CONNECTED AS CLOSE AS PRACTICAL TO
THE WALL OF THE ENCLOSURE, BUT IN
NO CASE MORE THAN THE SIZE OF THE
CONDUIT OR 50MM, WHICHEVER IS THE
LESSER.
 TO PREVENT IGNITION OF GROUP A, B, C
AND D ATMOSPHERES - SEE
INSTRUCTION FOR CHEMICAL
COMPATIBILITY
Avertissement:
 NE PAS OUVRIR UN PRESENCE
D'ATMOSPHERE EXPLOSIVE
 NE PAS OUVRIR ENERGIE
 DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
 HAUT TENSION, RISK DE CHOC.
ATTENDEZ 5 MINUTES APRES AVOIR
DEBRANCHE L'ALIMENTATION AVANT
D'OUVRIR LA BOITIER
 NE PAS PEINTURER
 POUR RÉDUIRE LE RISQUE
D'INFLAMMATION DES ATMOSPHÈRES
DANGEREUSES, LE PREMIER CONDUIT DE
CONDUIT DOIVENT AVOIR UN RACCORD
D'ÉTANCHÉITÉ RACCORDÉ À MOINS DE 18
E2S Warning Signals
Impress House, Mansell Road, Acton, London W3 7QH
Document No. D191-00-201-IS
Issue 3
28-11-22
D1xB2X05
D1xB2X10
D1xB2X15
D1xB2X21
POUCES DE L'ENFERMEMENT. POUR
SUBSÉQUENT LES CONDUITES DE
CONDUIT LA DISTANCE ENTRE LA
SURFACE DE LA MASSE DE REMPLISSAGE
AU PLUS PRÈS DE L'ENVELOPPE DOIT
ÊTRE AUSSI PETITE QUE CE QUI EST
RÉALISABLE MAIS EN AUCUN CAS
SUPÉRIEURE À LA PLUS PETITE DES
DIMENSIONS CORRESPONDANT À LA
TAILLE DU CONDUIT OU À 50 MM.
 POUR PRÉVENIR L'INFLAMMATION DES
ATMOSPHÈRES DES GROUPES A, B, C ET
D-VOIR L'INSTRUCTION POUR LA
COMPATIBILITÉ CHIMIQUE
2) Rating & Marking Information
2.1 Fire Alarm Ratings
The Following models are certified as visual alarm devices for
fire alarm use – private mode visual alarm devices in
accordance with UL1638 / CAN/ULC-S526 when used with
Clear or Red lens covers:
D1xB2X05DC024 / D1xB2X10DC024 / D1xB2X15DC024 /
D1xB2X21DC024
On-axis light output per UL1638:
Model
D1XB2
X05DC024 - 1Hz
X05DC024 - 1.33Hz
X05DC024 - 1.5Hz
X10DC024 - 1Hz
X10DC024 - 1.33Hz
X10DC024 - 1.5Hz
X15DC024 - 1Hz
2X15DC024 - 1.33Hz
X15DC024 - 1.5Hz
X21DC024 - 1Hz
X21DC024 - 1.33Hz
X21DC024 - 1.5Hz
www.e2s.com
Light Intensity in cd
Clear Lens
Red Lens
20.44
5.89
14.47
4.17
11.1
2.13
69.81
23.66
49.42
16.75
35.71
8.57
98.61
31.83
69.81
22.53
50.44
11.53
215.85
70.74
155.12
50.84
137.47
45.05
Tel: +44 (0)208 743 8880
Sheet 1 of 9

Advertisement

Table of Contents
loading

Summary of Contents for E2S D1xB2X05

  • Page 1 INSTRUCTION MANUAL D1xB2X05, D1xB2X10, D1xB2X15 & D1xB2X21 Xenon Beacons For use in Hazardous Locations D1xB2X05 D1xB2X10 D1xB2X15 D1xB2X21 1) Warnings POUCES DE L'ENFERMEMENT. POUR SUBSÉQUENT LES CONDUITES DE CONDUIT LA DISTANCE ENTRE LA  DO NOT OPEN WHEN AN EXPLOSIVE...
  • Page 2 Class III Div 1 Ta -55°C to +80°C Class I Zone 1 AEx db IIC T5 Ta -55°C to +50°C Zone 21 AEx tb IIIC T153°C Ta -55°C to +70°C E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No.
  • Page 3 Ex tb IIIC T153°C Ta -55°C to +70°C Ex db IIC T5 Gb Ta -55°C to +50°C Ex tb IIIC T116°C Db Ta -55°C to +70°C E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No.
  • Page 4 Explosive dust air mixture not likely to occur in Zone 22 normal operation, and if it does, it will only exist for a short time. E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No.
  • Page 5: Installation

    The D1xB2X beacon can be mounted using one of three methods. conducting surfaces. Additionally, cleaning of the equipment should be done only with a damp cloth. E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No.
  • Page 6: Cable Connections

    Ensure the O-ring seal is in place and undamaged. E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No.
  • Page 7: Line Monitoring

    Fig. 6: Internal and External Earth Locations resistor legs as shown in Fig. 5a, fit the resistor across the two terminals, as shown in Fig. 5b. E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No.
  • Page 8 Avoid looking directly at the light source for extended periods of time. The Beacon lens cover is interchangeable, contact E2S Ltd for a replacement lens cover available in various colours. The D1xB2X beacon can produce different flash patterns as shown in Table 1.
  • Page 9: Maintenance, Overhaul & Repair

    Hardware Fault Tolerance Diagnostic Coverage > PFD (hazardous failure) x 10 Proof Test Interval Up to 1 year E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH www.e2s.com Tel: +44 (0)208 743 8880 Document No. D191-00-201-IS Issue 3 28-11-22...
  • Page 12: Eu Declaration Of Conformity

      United Kingdom    Authorised Representative:  E2S Warnsignaltechnik UG        Charlottenstrasse 45‐51        72764 Reutlingen        Germany      Equipment Type:   D1xB2X05, D1xB2X10, D1xB2X15, D1xB2X21, D1xB2LD2, D1xJ2    Directive 2014/34/EU: Equipment and Protective Systems for use in Potentially Explosive Atmospheres (ATEX)  Notified Body for EU type Examination (Module B):  UL International Demko A/S  Notified Body No.: 0539  Borupvang 5A, 2750 Ballerup, Denmark  EU‐type Examination Certificate (Module B):  DEMKO 19 ATEX 2009X Rev. 1  Notified Body for Quality Assurance Notification / Conformity to EU‐type  Sira Certification Service  based on  Notified Body No.: 2813  quality assurance of the production process (Module D):  CSA Group Netherlands B.V, Utrechtseweg 310, 6812 AR, Arnhem, Netherlands  Quality Assurance Notification (Module D):  SIRA 05 ATEX M342  Provisions fulfilled by the equipment:  II 2G Ex d IIC T6…T3 Gb  II 2D Ex tb IIIC T95°C…T169°C Db  ...
  • Page 13   Manufacturer:      European Safety Systems Ltd.        Impress House, Mansell Road, Acton        London, W3 7QH        United Kingdom    Equipment Type:     D1xB2X05, D1xB2X10, D1xB2X15, D1xB2X21, D1xB2LD2, D1xJ2    Directive  UKSI 2016:1107 (as amended by UKSI 2019:696) – Schedule 3A, Part 1 : Product or Protective System Intended for use in Potentially Explosive Atmospheres   (UKCA)    Notified Body for UK type Examination (Module B):  UL International (UK) Ltd  Notified Body No.: 0843  Unit 1‐3 Horizon Kingsland Business Park, Wade Road,  Basingstoke, Hampshire RG24 8AH UK  UK‐type Examination Certificate (Module B):  UL21UKEX2130X Notified Body for Quality Assurance Notification / Conformity to EU‐type  Sira Certification Service  based on  Notified Body No.: 0518  quality assurance of the production process (Module D):  Rake Lane, Eccleston, Chester CH4 9JN, UK  Quality Assurance Notification (Module D):  CSAE 22UKQAN0046 ...
  • Page 14 Page left Intentionally blank...
  • Page 15 Page left Intentionally blank...
  • Page 16 Page left Intentionally blank...

Table of Contents