hit counter script
Download Print this page
E2S D105AX Instruction Manual

E2S D105AX Instruction Manual

Metal housed alarm tone and voice annunciation sounder/sounder beacon range

Advertisement

Quick Links

1)
Introduction
The Appello tone and speech annunciation
sounder has three different styles in DC.
D105AX
Sounder
DL105AXX Sounder Beacon (Xenon)
DL105AXH Sounder Beacon (LED)
These Sounder units share a common set of
functions:-
4 stages, each stage can record up to 30
seconds of CD quality audio.
Facility to record via an on board microphone
or a line in input.
The recorded message can be played back
proceeded either with or without the choice
of one of forty five tones.
The Beacon functions are either:-
Xenon Strobe:
o
1Hz flash rate
o
1.5Hz flash rate
o
Double strike flash pattern
LED:
o
Steady
o
2Hz flash rate
2)
Operating and Marking
All
units
have
the
requirements and limitations.
Sounder only outputs
Unit Type No.
Voltage Range
D105AX
24Vdc
Max Current 256mA @ 30Vdc
DL105AXX & DL105AXH sounder beacon units -
Add selected sounder & beacon currents to
calculate total current required.
Beacon only outputs
Unit Type No.
Voltage Range
Xenon Beacon
12Vdc
24Vdc
LED Beacon
24Vdc
Max Current 166mA @ 30Vdc
Operating Temp: -25 to +55C
IP Rating:
Type 4 / 4X / 3R / 13 , IP66
Marking:
European Safety Systems Ltd.
Document No. D172-00-051-IS_Issue_B
Annunciation Sounder/Sounder Beacon Range.
following
operating
Current
10-30Vdc
256mA
Current
10-14Vdc
500mA
20-28Vdc
250mA
10-30Vdc
157mA
Impress House, Mansell Road, Acton, London W3 7QH
16-11-22
Sheet 1 of 9
INSTRUCTION MANUAL
Metal Housed Alarm Tone and Voice
3)
Installation & Wiring Requirements
D105AX
DL105AXX & DL105AXH
Always de-energize unit before removing cover.
The installation of the units must be in accordance
with any local codes that may apply and should
only be carried out by a competent trained
electrical engineer.
The power terminals on the control unit are clearly
marked and will accept up to 1.5mm
The DL105AXX & DL105AXH units will have the
beacon already prewired to the unit so no extra
wiring is required.
sales@e2s.com
www.e2s.com
2
cable.
DC Terminals
On main PCB.
++ = Positive
- - = Negative
Tel: +44 (0)208 743 8880
Fax: +44 (0)208 740 4200

Advertisement

loading

Summary of Contents for E2S D105AX

  • Page 1 INSTRUCTION MANUAL Metal Housed Alarm Tone and Voice Annunciation Sounder/Sounder Beacon Range. Introduction Installation & Wiring Requirements The Appello tone and speech annunciation sounder has three different styles in DC. D105AX • D105AX Sounder • DL105AXX Sounder Beacon (Xenon) •...
  • Page 2 S2 terminal, for Stage 3 link the -ve supply 2Hz flashing mode to the S3 terminal etc. European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. D172-00-051-IS_Issue_B...
  • Page 3 The "Mass Erase" can also be used to reset the unit if any functionality is lost. European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No.
  • Page 4 Quick Ref - Recording Mode (Stage 1 illustrated) European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. D172-00-051-IS_Issue_B...
  • Page 5 Press action button: Stop recording European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. D172-00-051-IS_Issue_B 16-11-22...
  • Page 6 Press action button: Erase will begin - - - - erase complete European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. D172-00-051-IS_Issue_B 16-11-22...
  • Page 7 Reset Jumper J4 ‘ME’ to OFF position Quick Ref - Synchronising Two Sounders (All stages) European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. D172-00-051-IS_Issue_B...
  • Page 8 J6 to Sync off Set jumper J5 S/M on both units to Master position (on) European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. D172-00-051-IS_Issue_B 16-11-22...
  • Page 9 1KHz 1s on, 1s off Intermittent - PFEER Gen. Alarm Tone 38 Tone 34 Tone 29 European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. D172-00-051-IS_Issue_B 16-11-22...

This manual is also suitable for:

Dl105axxDl105axh