Parameter List
PNU
OP1 parameter name
*
: Ack.
Description
par.
H336
TeCntr B_SuppSet
*
Selection of binector to control application of supplementary setpoint
0 = Fixed value 0 (supplementary setpoint not applied)
1 = Fixed value 1 (supplementary setpoint continuously applied)
2 = Fixed value 0 (supplementary setpoint not applied)
3 = Binector B003
4 = Binector B004
etc.
PNU=538 Hex; Type=02; Normalization: 1==1; Block diag.: [21.1]
H337
TeCntr SetFilt_s
Setting of filter time for technology controller setpoint
PNU=539 Hex; Type=02; Normalization: 1==0.01 s; Block diag.: [21.2]
Control parameters
Note: Four different datasets for parameters H338 and H340 to H345 can be selected by means of the parameter set switchover function
H338
TeCntr PGain
Setting of P-gain of technology controller
PNU=53A Hex; Type=02; Normalization: 1==0.01; Block diag.: [21.5]
H339
TeCntr C_PGnAdpt
*
Selection of connector to be applied as the input quantity (P-gain factor)
for the purpose of P-gain adaptation
0 = Fixed value 0
1 = Fixed value 100 %
2 = Fixed value 0
3 = Connector K003
4 = Connector K004
etc.
PNU=53B Hex; Type=O2; Normalization: 1==1; Block diag.: [21.1]
H340
TeCntr PGadpt_x1
P-gain adaptation characteristic for technology controller - threshold 1
PNU=53C Hex; Type=O2; Normalization: 1==0.01 %; Block diag.: [21.2]
H341
TeCntr PGadpt_x2
P-gain adaptation characteristic for technology controller - threshold 2
PNU=53D Hex; Type=O2; Normalization: 1==0.01 %; Block diag.: [21.2]
H342
TeCntr PGadpt_y1
P-gain adaptation characteristic for technology controller
Minimum value of y (P-gain factor) when x ≤ x1
PNU=53E Hex; Type=O2; Normalization: 1==0.01; Block diag.: [21.1]
H343
TeCntr PGadpt_y2
P-gain adaptation characteristic for technology controller
Maximum value of y (P-gain factor) when x ≥ x2
PNU=53F Hex; Type=O2; Normalization: 1==0.01; Block diag.: [21.1]
H344
TeCntr ResetTime
Setting of reset time for technology controller
The integral component of the technology controller can be deactivated
with H351xxx0
PNU=540 Hex; Type=02; Normalization: 1==0.001s; Block diag.: [21.6]
H345
TeCntr R-T∗1000
Selection of factor for reset time
0
Parameter H344 is multiplied by a factor of 1
1
Parameter H344 is multiplied by a factor of 1000
PNU=541 Hex; Type= O2; Normalization: 1==1; Block diag.: [21.6]
4-32
T100 Technology Board Manual for Software Module MS100 "Multi-Purpose Drive"
Value range
No. of
[unit]
indices
Selection text
Factory
setting
0 to 200
Ind: None
FS=0
0.00 to 600.00
Ind: 4
[s]
FS=0.00
0.10 to 200.00
Ind: 4
FS=3.00
0 to 180
Ind: None
FS=0
0.00 to 200.00
Ind: 4
[%]
FS=0.00
0.00 to 200.00
Ind: 4
[%]
FS=100.00
0.10 to 30.00
Ind: 4
FS=1.00
0.10 to 30.00
Ind: 4
FS=1.00
0 to 60.000
Ind: 4
[s]
FS=3.000
0 to 1
Ind: 4
FS=0
Value ∗1
Value ∗1000