Master Drives
CBD
06/29/00
PKE Example 2: Set value of parameter P554.1 = 3001 hex
This example details the decoding of the task PKE and the response PKE of example 2 in the Use of PKW
object section 4.2.1 previously.
Task ID (request from master)
(PKE):
P554 (=22A hex): Source for the ON/OFF1 command (control word 1, bit 0)
Change parameter value (array, word) and store in the EEPROM.
Bit No.:
15
AK
Task ID
Binary value
1
1
HEX value
C
Bit 12..15:
Value = 12 (=
Bit 0..11:
Value = 554 (= "22A" hex); parameter number without set parameter change report
(PKE):
Response ID (response from drive)
P554 (=22A hex): Source for the ON/OFF1 command (control word 1, bit 0):
Transfer of new value of changed parameter (array, word).
Bit No.:
15
AK
Task ID
Binary value
0
1
HEX value
4
Bit 12..15:
Value = 4 (=
Bit 0..11:
Value = 554 (= "22A" hex); parameter number without set parameter change report
Fig. 4.1
Examples, parameter ID (PKE)
Siemens AG
477 759 4070 76 J AA-74
SIMOVERT MASTER DRIVES
4 Data transfer via DeviceNet
4.2 Parameter area (PKW)
4.2.1 Use of PKW object
4.2.1.4 Parameter ID (PKE)
Parameter ID (PKE)
12 11 10
SPM
Byte 1
0
0
0
0 1 0
0 0 1 0
2
"C" hex); change parameter value (array, word) and store in the EEPROM
Parameter ID (PKE)
12 11 10
SPM
Byte 1
0
0
0
0 1 0
0 0 1 0
2
"4" hex); transfer parameter value (array)
Betriebsanleitung / Operating Instructions
0
PNU
Byte 0
1
0
1 0
2
A
0
PNU
Byte 0
1
0
1 0
2
A
25