Setting The Output Voltage Setpoint - Siemens SITOP PSU8400 Equipment Manual

Table of Contents

Advertisement

3.3

Setting the output voltage setpoint

The output voltage setpoint can be set in the range 22 - 28 V using the buttons ⑥ and the
display ⑤.
When supplied, the output voltage setpoint is set to 24 V.
Changing the output voltage setpoint
Proceed as follows to change the output voltage setpoint:
In the display mode, by pressing the
menu item "U
the input mode and the display starts to flash.
By pressing the
steps. If the button is held, then the setting range is quickly run through either upward or
downward.
After the change has been completed, press the
display stops flashing and the newly set value is applied.
Note
If no button is pressed in the input mode for 10 seconds, then the system automatically
switches back to the display mode. A changed value or the selected setting is not applied.
SITOP PSU8400
Equipment Manual, 04.2024, A5E52642642-1-76
" is displayed. Then press the
set
or
button, you can now change the setpoint up or down in 0.1 V
Operator control at the device
3.3 Setting the output voltage setpoint
or
button, navigate through the menu until
button for at least 2 seconds. You enter
button for at least 2 seconds. The
29