Determining Wire and Fuse Sizes
The maximum motor currents in your application determines the recommended wore size.
The following table gives the wire size in AWG. The "Power Lines" column applies to the
inverter input power, output wires to the motor, the earth ground connection, and any other
components shown in the "Basic System Description" on page 2-7. The "Signal Lines"
column applies to any wire connecting to the two green connectors just inside the front
cover panel.
Motor Output
kW
HP
VT CT VT CT
0.2 0.1
¼
1/8
0.4 0.2
½
¼
0.55 0.4
¾
½
1.1 0.75 1.5
1
2.2 1.5
3
2
3.0 2.2
4
3
0.2 0.1
¼
1/8
0.4 0.2
½
¼
0.75 0.4
1
½
1.1 0.75 1.5
1
2.2 1.5
3
2
3.0 2.2
4
3
5.5 3.7
7.5
5
7.5 5.5
10
7.5
11
7.5
15
10
15
11
20
15
18.5 15
25
20
0.75 0.4
1
½
1.5 0.75
2
1
2.2 1.5
3
2
3.0 2.2
4
3
4.0 3.0
5
4
5.5 4.0
7.5
5
7.5 5.5
10
7.5
11
7.5
15
10
15
11
20
15
18.5 15
25
20
Note 1: Field wiring must be made by a UL-Listed and CSA-certified closed-loop terminal
connector sized for the wire gauge involved. Connector must be fixed by using
the crimping tool specified by the connector manufacturer.
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66ft. (20m).
Note 4: Use 18 AWG / 0.75mm
terminals).
Inverter Model
Power Lines
WJ200-001SF
AWG16 / 1.3mm
WJ200-002SF
WJ200-004SF
AWG12 / 3.3mm
WJ200-007SF
WJ200-015SF
AWG10 / 5.3mm
WJ200-022SF
WJ200-001LF
WJ200-002LF
AWG16 / 1.3mm
WJ200-004LF
WJ200-007LF
AWG14 / 2.1mm
WJ200-015LF
AWG12 / 3.3mm
WJ200-022LF
AWG10 / 5.3mm
WJ200-037LF
WJ200-055LF
AWG6 / 13mm
WJ200-075LF
AWG4 / 21mm
WJ200-110LF
AWG2 / 34mm
WJ200-150LF
WJ200-004HF
AWG16 / 1.3mm
WJ200-007HF
WJ200-015HF
WJ200-022HF
AWG14 / 2.1mm
WJ200-030HF
AWG12 / 3.3mm
WJ200-040HF
WJ200-055HF
AWG10/ 5.3mm
WJ200-075HF
AWG6 / 13mm
WJ200-110HF
AWG6 / 13mm
WJ200-150HF
2
wire for the alarm signal wire ([AL0], [AL1], [AL2]
Wiring
Signal Lines
2
(75°C only)
2
(75°C only)
2
2
2
(75°C only)
2
(75°C only)
2
18 to 28
(75°C only)
AWG / 0.14
2
to 0.75 mm
(75°C only)
shielded wire
2
(see Note 4)
(75°C only)
2
(75°C only)
2
2
2
(75°C only)
2
(75°C only)
2
(75°C only)
2
(75°C only)
10
Applicable
equipment
Fuse (UL-rated,
class J, 600V ,
Maximum
allowable current)
10A
20A
30A
10A
15A
20A
30A
2
60A
80A
80A
10A
15A
30A
50A
50A