Excessively Low Voltage Or Excessively High Voltage For The Inverter For Ivx Series - Hitachi RAS-(3-6)HVRNM2E Service Manual

Utopia dc-inverter ivx/(2/2.5)hp/es series air conditioner
Table of Contents

Advertisement

8 Troubleshooting
06
Alarm code
The RUN LED flickers and "ALARM" is displayed on the remote control switch.
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section.
The unit number and the alarm code are displayed on the display of the outdoor unit PCB.
-
This alarm code is displayed when the voltage between terminal "P" and "N" of IPM is insufficient and the alarm has
three occurrences in 30 minutes. If the number of occurrences is smaller than two, the retry operation is performed.
The alarm code "06." Means fan controller abnormal operation.
RAS-(3-6)HVRNM2E
Restart the operation
Is the power supply voltage
230V ±10%
Yes
Is the voltage over 187V during
operation?
Yes
Does the voltage fall during
the operation because of the
operation of other apparatus?
No
Does LED201 on PCB2
ON after compressor's
electromagnetic switches
(CMC) turn ON?
No
Is connection correctly
between DipIPM and capacitors
(CB1 and CB2), DCL or CMC?
Yes
Is the DC voltage over 240V?
No
224
SMGB0064 rev.0 - 08/2011

Excessively low voltage or excessively high voltage for the inverter for IVX Series

No
No
Yes
How is the
Yes
compressor
operation?
No
Be extremely carefull because of the
high voltage
Yes
Check capacitors (CB1, 2)
Normal
Frequency can increase
higher than 60 Hz
Compressor stops
immediately (lower
than 20 Hz)
Compressor stops when
frequency increases
(Approx. 20 Hz to 60 Hz)
Faulty
Check the wiring and the
cable capacity
Faulty PCB2. Replace it
Connect correctly
Replace the capacitors
Capacitors have high voltage.
Be extremely carefull *1)
Faulty PCB2. Replace it
Check the wiring PCB2 and
capacitors CB.
In case the wiring is correct,
replace the PCB2.