INSTALLATION IN DETAIL

The Nectre 800 Wall Heater is designed to be built in to a wall enclosure and
may be elevated from the floor. The wall enclosure may be constructed of non
combustible material such as masonry or Hebel blocks or may be constructed of
timber and steel framing and clad with plaster board and fibre-cement sheet (see
drawing).
Installation must comply with the standard AS/NZS 2918:2001. (Domestic Solid
Fuel Burning Appliances – Installation)
Clearances
The clearances from the wall heater to combustible materials must not be less
than the following:
(Note that plasterboard over a timber frame is a combustible surface)
Rear wall clearance
Side wall clearance
Front of heater to existing wall - 500mm
Underside clearance
Ceiling clearance
- 25mm (within the enclosure)
- 200mm (within the enclosure)
- 200mm
- 1170mm